Plan Review Notes
Plan Review Notes For Permit 17051237
Permit Number 17051237
Review Stop B
Sequence Number 1
Notes
Date Text
2017-06-05 09:49:39PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 REVISION DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE SIMPSON TS 18 STRAPS THAT ARE SPECIFIED FOR THE
 ROOF TO WALL CONNECTORS ARE FOR TENSION AND DO NOT
 PROVIDE RESISTANCE TO LATERAL FORCES THAT ARE REQUIRED.
 FBC-R802.1.7.5
  
 2) REVISED ENERGY FORMS SHOWING THE CHANGES WILL NEED
 TO BE SUBMITTED AND REVIEWED. FBC ENERGY CONSERVATION
 R103.2