| 2017-06-09 12:13:01 | 2 ND REVIEW |
| | |
| | |
| | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | THE COMMENTS MUST BE ADDRESSED SPECIFICALLYAND |
| | INFORMATION RELATING TO THEM PROVIDED ON THE PLAN |
| | SHEETS OR AN ATTACHED LETTER. |
| | |
| | |
| | |
| | |
| | 1) THERE IS INSUFFICIENT DETAIL SUBMITTED TO COMPLETE |
| | AN ACCURATE REVIEW PER THE FLORIDA FIRE PREVENTION |
| | CODE. |
| | |
| | LACKING INFORMATION NOTED BELOW |
| | |
| | FAILED |
| | |
| | |
| | 2) CONFIRMED |
| | |
| | |
| | 3) THERE IS NO NOTE OF REVIEW AND/OR COMPLIANCE WITH |
| | THE FLORIDA FIRE PREVENTION CODE, 5TH EDITION. |
| | |
| | PLEASE ENSURE A REVIEW AND A NOTE OR COMPLIANCE. |
| | |
| | NOT PROVIDED |
| | |
| | FAILED |
| | |
| | |
| | 4) CONFIRMED |
| | |
| | |
| | |
| | 5) IT APPEARS THAT TWO NEW DOORS ARE BEING INSTALLED. |
| | THERE IS NO DOOR SCHEDULE AND/OR HARDWARE MEETING THE |
| | REQUIREMENTS OF NFPA 101, CHAPTER 7, MEANS OF EGRESS. |
| | |
| | PLEASE PROVIDE. |
| | |
| | NOT PROVIDED |
| | |
| | FAILED |
| | |
| | |
| | |
| | 6) THERE IS NO INDICATIONS OF ANY EXISTING FIRE ALARM |
| | OR FIRE SPRINKLER SYSTEM. |
| | |
| | ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR |
| | CEILINGS REQUIRE AN EVALUATION OF THE FIRE ALARM AND |
| | SPRINKLER SYSTEM FOR CODE COVERAGE AND COMPLIANCE BY |
| | CERTIFIED LIFE SAFETY CONTRACTORS. |
| | THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE |
| | SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE |
| | CONSTRUCTION PERIOD. |
| | ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER |
| | SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND |
| | BY CERTIFIED LIFE SAFETY CONTRACTORS. |
| | |
| | PLEASE PROVIDE AN APPLICABLE NOTE. |
| | |
| | NOT PROVIDED |
| | |
| | FAILED |
| | |
| | |
| | 7) THERE IS NO INDICATION OF A WALL SCHEDULE. |
| | |
| | PLEASE PROVIDE. |
| | |
| | NOT PROVIDED |
| | |
| | FAILED |
| | |
| | |
| | |
| | 8) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 9) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |