Plan Review Notes
Plan Review Notes For Permit 17051202
Permit Number 17051202
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2017-05-30 12:33:28THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) THERE IS INSUFFICIENT DETAIL SUBMITTED TO COMPLETE
 AN ACCURATE REVIEW PER THE FLORIDA FIRE PREVENTION
 CODE.
  
  
 2) THERE IS NO TITLE BLOCK INDICATING THE ADDRESS,
 SUITE # OR DESIGNER NAME ON THE DRAWING SHEETS.
  
 PLEASE PROVIDE.
  
  
 3) THERE IS NO NOTE OF REVIEW AND/OR COMPLIANCE WITH
 THE FLORIDA FIRE PREVENTION CODE, 5TH EDITION.
  
 PLEASE ENSURE A REVIEW AND A NOTE OR COMPLIANCE.
  
  
 4) THERE IS NO SCOPE OF WORK.
  
 PLEASE PROVIDE A DETAILED SCOPE OF WORK NOTE OR
 NARRATIVE.
  
  
  
 5) IT APPEARS THAT TWO NEW DOORS ARE BEING INSTALLED.
 THERE IS NO DOOR SCHEDULE AND/OR HARDWARE MEETING THE
 REQUIRMENTS OF NFPA 101, CHAPTER 7, MEANS OF EGRESS.
  
 PLEASE PROVIDE.
  
  
 6) THERE IS NO INDICATIONS OF ANY EXISTING FIRE ALARM
 OR FIRE SPRINKLER SYSTEM.
  
 ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR
 CEILINGS REQUIRE AN EVALUATION OF THE FIRE ALARM AND
 SPRINKLER SYSTEM FOR CODE COVERAGE AND COMPLIANCE BY
 CERTIFIED LIFE SAFETY CONTRACTORS.
 THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
 ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
 PLEASE PROVIDE AN APPLICABLE NOTE.
  
  
 7) THERE IS NO INDICATION OF A WALL SCHEDULE.
  
 PLEASE PROVIDE.
  
  
 8) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 9) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  