| 2017-06-02 07:33:21 | 2014 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 17051202 |
| | ADD: 410 EVERNIA ST. SUITE: MANAGEMENT OFFICE |
| | CONT: HARTZELL |
| | TEL: 954-957-9711 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: FRI. JUNE 02/2017 |
| | ACTION: DENIED |
| | |
| | 1) VALUE OF THE PROJECT IS LOW, PLEASE PROVIDE AN |
| | ACCURATE VALUE FOR THIS PROJECT. PERMIT FEES/ PLAN |
| | REVIEW: |
| | W P B ADMINISTRATIVE CODE 108.3* BUILDING PERMIT |
| | VALUATION. IF, IN THE OPINION OF THE BUILDING OFFICIAL, |
| | THE CLAIMED VALUATION OF BUILDING, ALTERATION, |
| | STRUCTURE, ELECTRICAL, GAS, MECHANICAL, OR PLUMBING |
| | SYSTEMS APPEARS TO BE UNDER ESTIMATED ON THE |
| | APPLICATION, THE PERMIT SHALL BE DENIED. FOR PERMITTING |
| | PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE |
| | TOTAL REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND |
| | SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE |
| | STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR |
| | FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR |
| | BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING |
| | COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| | VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED |
| | DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| | (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS |
| | FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE |
| | CONGRESS. |
| | |
| | 2) THE SUBMITTED PLANS DOES NOT INCLUDE A TITLE STRIP |
| | OF WHO THE AUTHOR IS OF THE PLANS. THE QUALIFIER FOR |
| | THE COMPANY NEEDS TO PRINT THEIR NAME, SIGN THEIR NAME |
| | AND PRINT THEIR LICENSE NUMBER ON THE PLANS AND |
| | IDENTIFY THE PROJECT BY ADDRESS. 107.2.1. INFORMATION |
| | ON THE CONSTRUCTION DOCUMENTS. |
| | |
| | 3) THE PLANS ARE MISSING INFORMATION: 2014 FLORIDA |
| | BUILDING CODE W 2014 WEST PALM BEACH AMENDMENTS TO THE |
| | FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION |
| | 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS |
| | 107.3.5.1 COMMERCIAL BUILDINGS: |
| | 107.3.5.1.1 BUILDING |
| | 3A) MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED BY |
| | FBC-B TABLE 503 |
| | 3B) OCCUPANCY GROUP |
| | 3C) PLANS DRAWN TO SCALE |
| | 3D) NEW WALL CONSTRUCTION DETAIL/ CUT SECTION/ |
| | MATERIALS/ ANCHORAGE OF WALL/ HIGHRISE |
| | 3E) NEW DOOR SIZE, NOT NOTED. 2014 FBC-B 1008.1.1 |
| | MINIMUM DOOR SIZE IS A 32 INCH CLEAR WIDTH OR A 2 FT. |
| | 10 INCH DOOR. |
| | |
| | 4) 2014 FBC-ACCESS. CODE 404.2.6 DOORS IN SERIES AND |
| | GATES IN SERIES. THE DISTANCE BETWEEN TWO HINGED OR |
| | PIVOTED DOORS IN SERIES AND GATES IN SERIES SHALL BE 48 |
| | INCHES MINIMUM PLUS THE WIDTH OF DOORS SWINGING INTO |
| | THE SPACE. |
| | 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | THIS REVIEW CYCLE A THOROUGH REVIEW COULD NOT BE |
| | COMPLETED AND ADDITIONAL AND OR NEW COMMENTS MAY OCCUR |
| | ON SUBSEQUENT REVIEWS. |
| | |