Plan Review Notes
Plan Review Notes For Permit 17051201
Permit Number 17051201
Review Stop E
Sequence Number 1
Notes
Date Text
2017-06-08 08:29:48CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS:
  
 1. PROVIDE DETAILED RISER DIAGRAM, INCLUDING WIRE,
 CONDUIT, AND GROUNDING ELECTRODE CONDUCTOR SIZE. FBC
 107.3.5, NEC 215.5
 2. IS THERE AN EXISTING SERVICE TO THIS LOCATION, OR IS
 IT FED FROM THE MAIN HOUSE? IF THERE IS AN EXISTING
 METER, PROVIDE DETAILS ON THE RISER DIAGRAM, SHOWING
 SIZES TO BE REPLACED. FBC 107.3.5, NEC 215.5
 3. NOTE ON PLAN STATES THAT ALL RECEPTACLES SHALL BE
 AFCI PROTECTED. PROVIDE CORRECTION. CODE REQUIRES ALL
 OUTLETS, INCLUDING RECEPTACLES AND LIGHTING TO BE AFCI
 PROTECTED. "ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT,
 SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN
 FAMILY ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS,
 LIBRARIES, DENS, BEDROOMS, SUNROOMS, RECREATIONS ROOMS,
 CLOSETS, HALLWAYS AND SIMILAR ROOMS OR AREAS SHALL BE
 PROTECTED BY A COMBINATION TYPE ARC-FAULT CIRCUIT
 INTERRUPTER INSTALLED TO PROVIDE PROTECTION OF THE
 BRANCH CIRCUIT." NEC 210.12 FBC RE3902.12
 4. NOTE ON PLAN STATES THAT RECEPTACLES SHALL BE TAMPER
 RESISTANT PER NEC 406.11. THE PROPER CODE SECTION FOR
 THIS IS 406.12. PROVIDE CORRECTION. FBC 107.2.1, NEC
 406.12, FBC RE4002.14
 5. THERE IS A DISCREPANCY WITH THE HOT WATER HEATER
 (HWH). THE ELECTRICAL PLAN STATES THAT THERE ARE 2 HWH,
 EACH RATED AT 4.5 KW. THE PLUMBING PLAN STATES THAT THE
 RATING IS 12 KW, AND IT APPEARS ON THE PLUMBING PLAN
 THAT THERE IS ONLY ONE OF THESE. PLEASE CLARIFY AND/OR
 CORRECT. UPDATE LOAD CALCULATION IF REQUIRED. FBC
 107.2.1 NEC 220
 6. PROVIDE SWITCH CONTROLLED LIGHT AT EACH ENTRY/EXIT
 DOOR WITH ACCESS TO GRADE. "AT LEAST ONE
 WALL-SWITCH-CONTROLLED LIGHTING OUTLET SHALL BE
 INSTALLED IN HALLWAYS, STAIRWAYS, ATTACHED GARAGES, AND
 DETACHED GARAGES WITH ELECTRIC POWER. AT LEAST ONE
 WALL-SWITCH-CONTROLLED LIGHTING OUTLET SHALL BE
 INSTALLED TO PROVIDE ILLUMINATION ON THE EXTERIOR SIDE
 OF EACH OUTDOOR EGRESS DOOR HAVING GRADE LEVEL ACCESS,
 INCLUDING OUTDOOR EGRESS DOORS FOR ATTACHED GARAGES AND
 DETACHED GARAGES WITH ELECTRIC POWER. A VEHICLE DOOR IN
 A GARAGE SHALL NOT BE CONSIDERED AS AN OUTDOOR EGRESS
 DOOR. WHERE ONE OR MORE LIGHTING OUTLETS ARE INSTALLED
 FOR INTERIOR STAIRWAYS, THERE SHALL BE A WALL SWITCH AT
 EACH FLOOR LEVEL AND LANDING LEVEL THAT INCLUDES AN
 ENTRYWAY TO CONTROL THE LIGHTING OUTLETS WHERE THE
 STAIRWAY BETWEEN FLOOR LEVELS HAS SIX OR MORE RISERS".
 NEC 210.70(A)(2)(B) FBC RE3903.3
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  