| Plan Review Notes For Permit 17051195 |
| Permit Number |
17051195 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-05-30 06:09:29 | 1.) SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE | | | LENGTH OF ALL CUT SECTIONS OF PIPE PER 2014 FBC-FUEL | | | GAS, SECS. 402.4.1, 402.4.2. OR 2014 FBC-RES SEC. | | | G2413. | | | 2) INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM | | | ON THE PLAN PER 2014 FBC-FUEL GAS SEC.402.2 OR FBC RES. | | | SEC. G2413.2. | | | 3) SUBMIT MANUFACTURER?S SPECIFICATION SHEETS / | | | INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY | | | COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND | | | FBC-2014 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2014 | | | FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED | | | AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS | | | APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF | | | INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1. | | | 4) SUBMIT TWO COPIES OF THE SIZING TABLES USED IN THE | | | DESIGN FOR THIS GAS SYSTEM OR PLACE A NOTE ON BOTH SETS | | | OF PLANS LISTING THE SIZING TABLES FROM THE GAS CODE OR | | | NFPA STANDARD THAT WERE USED IN THE DESIGN OF THIS | | | SYSTEM. FGC SEC.402.3, FBCR SEC. G 2413.3. | | | 5) SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS. | | | A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY | | | AHEAD OF EACH MP REGULATOR. FBC-FUEL GAS SEC.409.4, | | | FBC-RESIDENTIAL SEC. G 2420.4. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|