Plan Review Notes
Plan Review Notes For Permit 17051107
Permit Number 17051107
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2017-06-05 16:29:07NFPA 1.14.2 THE APPLICANT SHALL BE RESPONSIBLE TO
 ENSURE THAT THE FOLLOWING CONDITIONS ARE MET:
 (1)THE CONSTRUCTION DOCUMENTS INCLUDE ALL OF THE FIRE
 PROTECTION REQUIREMENTS. (2) THE SHOP DRAWINGS ARE
 CORRECT AND IN COMPLIANCE WITH THE APPLICABLE CODES AND
 STANDARDS.
  
 NFPA 101-30.3.4.5 SMOKE ALARMS. SMOKE ALARMS SHALL BE
 INSTALLED IN ACCORDANCE WITH 9.6.2.10 IN EVERY SLEEPING
 AREA, OUTSIDE EVERY SLEEPING AREA IN THE IMMEDIATE
 VICINITY OF THE BEDROOMS, AND ON ALL LEVELS OF THE
 DWELLING UNIT, INCLUDING BASEMENTS.
  
 SHEET FA 6.04 A & B - THERE ARE NO SMOKE DETECTORS
 INDICATED IN THE ELECTRIC ROOMS AND MECHANICAL CLOSETS,
 PLEASE REVIEW AND JUSTIFY OR ADD.
  
 SHEET FA 6.01 A & B - THERE ARE NO SMOKE DETECTORS
 INDICATED IN THE TENANT STORAGE SPACES. PLEASE REVIEW
 AND JUSTIFY OR ADD.
  
 SHEET FA 6.25 - THERE IS NO SMOKE DETECTION INDICATED
 IN THE STORAGE ROOM. PLEASE REVIEW AND JUSTIFY OR ADD.
  
 SHEET FA 6.26 - THERE IS NO SMOKE DETECTION INDICATED
 IN THE STORAGE ROOM. PLEASE REVIEW AND JUSTIFY OR ADD.
  
 SHEET FA 6.26 - THERE ARE BOTH SD AND HS INDICATED AT
 THE TOP OF THE HOISTWAY. PLEASE REVIEW AND JUSTIFY OR
 ADD. IS THERE A SPRINKLER HEAD LOCATED AT THE TOP OF
 THE HOISTWAY?
  
 WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET REVISION
 CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE ABOVE.
 ADDITIONAL COMMENTS MAY BE PROVIDED ON THE RE-SUBMITTAL
 OF THE ABOVE.
 SHEET FA 6.01 A & B - THERE ARE BOTH SD AND HS
 INDICATED AT THE BOTTOM OF THE HOISTWAY. PLEASE REVIEW
 AND JUSTIFY OR ADD. IS THERE A SPRINKLER HEAD LOCATED
 AT THE BOTTOM OF THE HOISTWAY?
  
 NFPA 101-9.6.2.10.3* IN NEW CONSTRUCTION, WHERE TWO OR
 MORE SMOKE ALARMS ARE REQUIRED WITHIN A DWELLING UNIT,
 SUITE OF ROOMS, OR SIMILAR AREA, THEY SHALL BE ARRANGED
 SO THAT OPERATION OF ANY SMOKE ALARM SHALL CAUSE THE
 ALARM IN ALL SMOKE ALARMS WITHIN THE DWELLING UNIT,
 SUITE OF ROOMS, OR SIMILAR AREA TO SOUND, UNLESS
 OTHERWISE PERMITTED BY THE FOLLOWING:
 (1) THE REQUIREMENT OF 9.6.2.10.3 SHALL NOT APPLY WHERE
 PERMITTED BY ANOTHER SECTION OF THIS CODE.
 (2) THE REQUIREMENT OF 9.6.2.10.3 SHALL NOT APPLY TO
 CONFIGURATIONS THAT PROVIDE EQUIVALENT DISTRIBUTION OF
 THE ALARM
 SIGNAL. 9.6.2.10.4 THE ALARMS SHALL SOUND ONLY WITHIN
 AN INDIVIDUAL DWELLING UNIT, SUITE OF ROOMS, OR SIMILAR
 AREA AND SHALL NOT ACTUATE THE BUILDING FIRE ALARM
 SYSTEM, UNLESS OTHERWISE PERMITTED BY THE AUTHORITY
 HAVING JURISDICTION. REMOTE ANNUNCIATION SHALL BE
 PERMITTED.
  
 PER NFPA 72 21.3.6 SMOKE DETECTORS SHALL NOT BE
 INSTALLED IN UNSPRINKLERED ELEVATOR HOISTWAYS UNLESS
 THEY ARE INSTALLED TO ACTIVATE THE ELEVATOR HOISTWAY
 SMOKE RELIEF EQUIPMENT.
  
 NFPA 72-7.4.4.1: WHERE AUDIBLE APPLIANCES ARE INSTALLED
 TO PROVIDE SIGNALS FOR SLEEPING AREAS, THEY SHALL HAVE
 A SOUND LEVEL OF LEAST 15 DB ABOVE THE AVERAGE AMBIENT
 SOUND LEVEL OR 5 DB ABOVE THE MAXIMUM SOUND LEVEL
 HAVING A DURATION OF AT LEAST 60 SECONDS OR A SOUND
 LEVEL OF AT LEAST 75 DBA, WHICHEVER IS GREATER,
 MEASURED AT THE PILLOW LEVEL IN AREA REQUIRED TO BE
 SERVED BY THE SYSTEM USING THE A-WEIGHTED SCALE (DBA).
  
 NFPA 72-10.18.2.4, 2010 VERIFICATION OF COMPLIANT
 INSTALLATION. WHERE REQUIRED, COMPLIANCE OF THE
 COMPLETED INSTALLATION WITH THE REQUIREMENTS OF THIS
 CODE, AS IMPLEMENTED VIA THE REFERRING CODE(S),
 SPECIFICATIONS, AND/OR OTHER CRITERIA APPLICABLE TO THE
 SPECIFIC INSTALLATION, SHALL BE CERTIFIED BY A
 QUALIFIED AND IMPARTIAL THIRD-PARTY ORGANIZATION
 ACCEPTABLE TO THE AUTHORITY HAVING JURISDICTION.
 10.18.2.4.1 VERIFICATION SHALL ENSURE THAT THE
 INSTALLED SYSTEM INCLUDES ALL COMPONENTS AND FUNCTIONS,
 THAT THOSE COMPONENTS AND FUNCTIONS ARE INSTALLED AND
 OPERATE AS REQUIRED, THAT THE SYSTEM HAS BEEN 100
 PERCENT ACCEPTANCE TESTED IN ACCORDANCE WITH CHAPTER
 14, AND THAT ALL REQUIRED DOCUMENTATION HAS BEEN
 PROVIDED TO THE SYSTEM OWNER.
  
 FRANK STALLWORTH, FIRE INSPECTOR I
 WEST PALM BEACH FIRE PREVENTION BUREAU
 500 N. DIXIE HWY
 WEST PALM BEACH, FLORIDA 33401
 OFFFICE: 561-840-4780
 FAX: 561-840-4774
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved