| Date |
Text |
| 2017-06-05 16:29:07 | NFPA 1.14.2 THE APPLICANT SHALL BE RESPONSIBLE TO |
| | ENSURE THAT THE FOLLOWING CONDITIONS ARE MET: |
| | (1)THE CONSTRUCTION DOCUMENTS INCLUDE ALL OF THE FIRE |
| | PROTECTION REQUIREMENTS. (2) THE SHOP DRAWINGS ARE |
| | CORRECT AND IN COMPLIANCE WITH THE APPLICABLE CODES AND |
| | STANDARDS. |
| | |
| | NFPA 101-30.3.4.5 SMOKE ALARMS. SMOKE ALARMS SHALL BE |
| | INSTALLED IN ACCORDANCE WITH 9.6.2.10 IN EVERY SLEEPING |
| | AREA, OUTSIDE EVERY SLEEPING AREA IN THE IMMEDIATE |
| | VICINITY OF THE BEDROOMS, AND ON ALL LEVELS OF THE |
| | DWELLING UNIT, INCLUDING BASEMENTS. |
| | |
| | SHEET FA 6.04 A & B - THERE ARE NO SMOKE DETECTORS |
| | INDICATED IN THE ELECTRIC ROOMS AND MECHANICAL CLOSETS, |
| | PLEASE REVIEW AND JUSTIFY OR ADD. |
| | |
| | SHEET FA 6.01 A & B - THERE ARE NO SMOKE DETECTORS |
| | INDICATED IN THE TENANT STORAGE SPACES. PLEASE REVIEW |
| | AND JUSTIFY OR ADD. |
| | |
| | SHEET FA 6.25 - THERE IS NO SMOKE DETECTION INDICATED |
| | IN THE STORAGE ROOM. PLEASE REVIEW AND JUSTIFY OR ADD. |
| | |
| | SHEET FA 6.26 - THERE IS NO SMOKE DETECTION INDICATED |
| | IN THE STORAGE ROOM. PLEASE REVIEW AND JUSTIFY OR ADD. |
| | |
| | SHEET FA 6.26 - THERE ARE BOTH SD AND HS INDICATED AT |
| | THE TOP OF THE HOISTWAY. PLEASE REVIEW AND JUSTIFY OR |
| | ADD. IS THERE A SPRINKLER HEAD LOCATED AT THE TOP OF |
| | THE HOISTWAY? |
| | |
| | WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET REVISION |
| | CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE ABOVE. |
| | ADDITIONAL COMMENTS MAY BE PROVIDED ON THE RE-SUBMITTAL |
| | OF THE ABOVE. |
| | SHEET FA 6.01 A & B - THERE ARE BOTH SD AND HS |
| | INDICATED AT THE BOTTOM OF THE HOISTWAY. PLEASE REVIEW |
| | AND JUSTIFY OR ADD. IS THERE A SPRINKLER HEAD LOCATED |
| | AT THE BOTTOM OF THE HOISTWAY? |
| | |
| | NFPA 101-9.6.2.10.3* IN NEW CONSTRUCTION, WHERE TWO OR |
| | MORE SMOKE ALARMS ARE REQUIRED WITHIN A DWELLING UNIT, |
| | SUITE OF ROOMS, OR SIMILAR AREA, THEY SHALL BE ARRANGED |
| | SO THAT OPERATION OF ANY SMOKE ALARM SHALL CAUSE THE |
| | ALARM IN ALL SMOKE ALARMS WITHIN THE DWELLING UNIT, |
| | SUITE OF ROOMS, OR SIMILAR AREA TO SOUND, UNLESS |
| | OTHERWISE PERMITTED BY THE FOLLOWING: |
| | (1) THE REQUIREMENT OF 9.6.2.10.3 SHALL NOT APPLY WHERE |
| | PERMITTED BY ANOTHER SECTION OF THIS CODE. |
| | (2) THE REQUIREMENT OF 9.6.2.10.3 SHALL NOT APPLY TO |
| | CONFIGURATIONS THAT PROVIDE EQUIVALENT DISTRIBUTION OF |
| | THE ALARM |
| | SIGNAL. 9.6.2.10.4 THE ALARMS SHALL SOUND ONLY WITHIN |
| | AN INDIVIDUAL DWELLING UNIT, SUITE OF ROOMS, OR SIMILAR |
| | AREA AND SHALL NOT ACTUATE THE BUILDING FIRE ALARM |
| | SYSTEM, UNLESS OTHERWISE PERMITTED BY THE AUTHORITY |
| | HAVING JURISDICTION. REMOTE ANNUNCIATION SHALL BE |
| | PERMITTED. |
| | |
| | PER NFPA 72 21.3.6 SMOKE DETECTORS SHALL NOT BE |
| | INSTALLED IN UNSPRINKLERED ELEVATOR HOISTWAYS UNLESS |
| | THEY ARE INSTALLED TO ACTIVATE THE ELEVATOR HOISTWAY |
| | SMOKE RELIEF EQUIPMENT. |
| | |
| | NFPA 72-7.4.4.1: WHERE AUDIBLE APPLIANCES ARE INSTALLED |
| | TO PROVIDE SIGNALS FOR SLEEPING AREAS, THEY SHALL HAVE |
| | A SOUND LEVEL OF LEAST 15 DB ABOVE THE AVERAGE AMBIENT |
| | SOUND LEVEL OR 5 DB ABOVE THE MAXIMUM SOUND LEVEL |
| | HAVING A DURATION OF AT LEAST 60 SECONDS OR A SOUND |
| | LEVEL OF AT LEAST 75 DBA, WHICHEVER IS GREATER, |
| | MEASURED AT THE PILLOW LEVEL IN AREA REQUIRED TO BE |
| | SERVED BY THE SYSTEM USING THE A-WEIGHTED SCALE (DBA). |
| | |
| | NFPA 72-10.18.2.4, 2010 VERIFICATION OF COMPLIANT |
| | INSTALLATION. WHERE REQUIRED, COMPLIANCE OF THE |
| | COMPLETED INSTALLATION WITH THE REQUIREMENTS OF THIS |
| | CODE, AS IMPLEMENTED VIA THE REFERRING CODE(S), |
| | SPECIFICATIONS, AND/OR OTHER CRITERIA APPLICABLE TO THE |
| | SPECIFIC INSTALLATION, SHALL BE CERTIFIED BY A |
| | QUALIFIED AND IMPARTIAL THIRD-PARTY ORGANIZATION |
| | ACCEPTABLE TO THE AUTHORITY HAVING JURISDICTION. |
| | 10.18.2.4.1 VERIFICATION SHALL ENSURE THAT THE |
| | INSTALLED SYSTEM INCLUDES ALL COMPONENTS AND FUNCTIONS, |
| | THAT THOSE COMPONENTS AND FUNCTIONS ARE INSTALLED AND |
| | OPERATE AS REQUIRED, THAT THE SYSTEM HAS BEEN 100 |
| | PERCENT ACCEPTANCE TESTED IN ACCORDANCE WITH CHAPTER |
| | 14, AND THAT ALL REQUIRED DOCUMENTATION HAS BEEN |
| | PROVIDED TO THE SYSTEM OWNER. |
| | |
| | FRANK STALLWORTH, FIRE INSPECTOR I |
| | WEST PALM BEACH FIRE PREVENTION BUREAU |
| | 500 N. DIXIE HWY |
| | WEST PALM BEACH, FLORIDA 33401 |
| | OFFFICE: 561-840-4780 |
| | FAX: 561-840-4774 |
| | [email protected] |
| | |