Plan Review Notes
Plan Review Notes For Permit 17051100
Permit Number 17051100
Review Stop M
Sequence Number 1
Notes
Date Text
2017-05-31 16:54:011ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17051100
 5/31/17
  
 RESULTS: DENIED.
  
 1) M2.1: PLEASE REVIEW BUILDING AND FIRE REVIEW
 COMMENTS CONCERNING THE ELEVATOR LOBBY, PENDING
 RESPONSES FROM THE DESIGN PROFESSIONALS AND POSSIBLE
 PLAN REVISIONS THE DUCTS PENETRATING THE LOBBY WALLS
 MAY REQUIRE FIRE/SMOKE DAMPERS.
  
 2) M2.1 & M6.1: HP-4 HAS A CAPACITY OF 1129 SUPPLY
 CFMS, HOWEVER THE MECHANICAL PLAN INDICATES THE UNIT
 MUST SUPPLY 1350 CFMS.
  
 3) M2.1: THERE IS AN 8X8 BRANCH DUCT CONNECTED TO THE
 MAIN TRUNK OF HP-5 WITH NO DIFFUSER.
  
 4) M2.1 & M6.1: HP=5 & HP-6A APPEAR TO BE OVERSIZED IN
 CAPACITY BASED ON THE SCHEDULE AND SUPPLY CFM
 DISTRIBUTION IN THE MECHANICAL PLAN- PLEASE CLARIFY.
  