Plan Review Notes
Plan Review Notes For Permit 17051100
Permit Number 17051100
Review Stop B
Sequence Number 1
Notes
Date Text
2017-05-30 16:22:32****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. REVISE PLAN TO SHOW COMPLIANCE WITH FBC B 713.14.1,
 708.1. IF AN EXCEPTION IS APPLICABLE, REVISE PLAN TO
 NOTE EXCEPTION. THE PLAN MAKES REFERENCE TO THE
 "ELEVATOR LOBBY" BUT NO FIRE RATINGS ARE SHOWN.
  
 2. SEPARATE PERMIT REQUIRED FOR ACCESS CONTROL; THIS
 WAS NOT REVIEWED AT THIS TIME AND WILL BE REVIEWED
 UNDER A SEPARATE PERMIT APPLICATION, FBC 107.
  
 3. A601 DOOR SCHEDULE IS LABELED "SECOND FLOOR", REVISE
 OR CLARIFY. WORK APPEARS TO BE LOCATED ON ONE FLOOR,
 10TH ONLY, FBC 107.
  
 4. DBPR WEBSITE DOES NOT SHOW THAT ENGINEER (R.A.KAMM,
 PE) HAS COMPLETED THE ADVANCED FLORIDA BUILDING CODE
 COURSE REQUIRED BY FLORIDA STATUTE 471.0195 (REQUIRED
 TO BE COMPLETED BY JUNE 30, 2016). CONTACT FBPE TO HAVE
 THEM UPDATE THE WEBSITE. THIS COMMENT WILL NOT DELAY
 PERMIT ISSUANCE; PLEASE HAVE ENGINEER ACKNOWLEDGE THAT
 COURSE HAS BEEN TAKEN AND FBPE INFORMED.
  
 5. G101 REFERS TO "CHIEF MEIZISO" AS AHJ; REVISE.
  
 6. REVISE PLAN TO INCLUDE COMPLIANCE METHOD ELECTED;
 FBC EB 301.1.
  
  