2017-05-24 19:12:30BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN (561) 805 6652
 E-MAIL: [email protected]
  
 COMMENTS BASED ON REVIEW "COURTYARD SITE PLAN"
 SUBMITTED VIA EMAIL ON 5/24/17:
  
 1) THE EVENT PLAN SHALL SHOW AT LEAST ONE WHEELCHAIR
 ACCESSIBLE WATERCLOSET AND LAVATORY FOR MALE GUESTS, AT
 LEAST ONE WHEELCHAIR ACCESSIBLE WATERCLOSET AND
 LAVATORY FOR FEMALE GUESTS, AND A SECOND REQUIRED
 FEMALE WATERCLOSET WHICH DOES NOT HAVE TO BE WHEELCHAIR
 ACCESSIBLE. THAT IS BASED ON ASSUMING THAT THE 200
 GUESTS WILL BE MADE UP OF 100 FEMALE GUESTS AND 100
 MALE GUESTS, AND USING TABLE 403.1 OF FLORIDA PLUMBING
 CODE, 5TH EDITION, FOR AN ASSEMBLY OCCUPANCY, AND
 SECTION 213.3.2 OF FLORIDA ACCESSIBILITY CODE, 2012
 EDITION.
  
 2) THE CANOPIES THAT WERE MENTIONED IN JOEL MEDGEBOW'S
 EMAIL SENT AT 2:30 PM ON 5/24/17, MUST BE SHOWN ON THE
 PLAN SO THAT THE LOCATION AND DIMENSIONS OF EACH CANOPY
 IS KNOWN, AS WELL AS A NOTE STATING WHETHER THE
 CANOPIES ARE TEMPORARY OR PERMANENT. IF THEY ARE
 TEMPORARY AND LARGER THAN 10 FEET BY 10 FEET, YOU ARE
 REQUIRED TO SUBMIT THE THE FLAME RETARDANT TREATMENT
 CERTIFICATES FOR THE FABRIC USED IN THE MANUFACTURING
 OF THE CANOPIES.
  
 3) ALL FIRE EXTINGUISHERS, FURNITURE, STRUCTURES,
 SCULPTURES, ARTWORK, DISPLAYS, OR OTHER OBJECTS,
 INCLUDING ANY FOOD/DRINK SERVICE AREAS AND/OR DJ STAND,
 THAT WILL BE IN THE SPACE OCCUPIED BY GUESTS MUST BE
 SHOWN ON THE PLAN SO THAT THE FIRE MARSHAL AND BUILDING
 DIVISION STAFF CAN SEE THE CIRCULATION ROUTES.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS