| 2017-05-24 19:12:30 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN (561) 805 6652 |
| | E-MAIL: [email protected] |
| | |
| | COMMENTS BASED ON REVIEW "COURTYARD SITE PLAN" |
| | SUBMITTED VIA EMAIL ON 5/24/17: |
| | |
| | 1) THE EVENT PLAN SHALL SHOW AT LEAST ONE WHEELCHAIR |
| | ACCESSIBLE WATERCLOSET AND LAVATORY FOR MALE GUESTS, AT |
| | LEAST ONE WHEELCHAIR ACCESSIBLE WATERCLOSET AND |
| | LAVATORY FOR FEMALE GUESTS, AND A SECOND REQUIRED |
| | FEMALE WATERCLOSET WHICH DOES NOT HAVE TO BE WHEELCHAIR |
| | ACCESSIBLE. THAT IS BASED ON ASSUMING THAT THE 200 |
| | GUESTS WILL BE MADE UP OF 100 FEMALE GUESTS AND 100 |
| | MALE GUESTS, AND USING TABLE 403.1 OF FLORIDA PLUMBING |
| | CODE, 5TH EDITION, FOR AN ASSEMBLY OCCUPANCY, AND |
| | SECTION 213.3.2 OF FLORIDA ACCESSIBILITY CODE, 2012 |
| | EDITION. |
| | |
| | 2) THE CANOPIES THAT WERE MENTIONED IN JOEL MEDGEBOW'S |
| | EMAIL SENT AT 2:30 PM ON 5/24/17, MUST BE SHOWN ON THE |
| | PLAN SO THAT THE LOCATION AND DIMENSIONS OF EACH CANOPY |
| | IS KNOWN, AS WELL AS A NOTE STATING WHETHER THE |
| | CANOPIES ARE TEMPORARY OR PERMANENT. IF THEY ARE |
| | TEMPORARY AND LARGER THAN 10 FEET BY 10 FEET, YOU ARE |
| | REQUIRED TO SUBMIT THE THE FLAME RETARDANT TREATMENT |
| | CERTIFICATES FOR THE FABRIC USED IN THE MANUFACTURING |
| | OF THE CANOPIES. |
| | |
| | 3) ALL FIRE EXTINGUISHERS, FURNITURE, STRUCTURES, |
| | SCULPTURES, ARTWORK, DISPLAYS, OR OTHER OBJECTS, |
| | INCLUDING ANY FOOD/DRINK SERVICE AREAS AND/OR DJ STAND, |
| | THAT WILL BE IN THE SPACE OCCUPIED BY GUESTS MUST BE |
| | SHOWN ON THE PLAN SO THAT THE FIRE MARSHAL AND BUILDING |
| | DIVISION STAFF CAN SEE THE CIRCULATION ROUTES. |
| | |
| | **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| | |
| | END OF REVIEW COMMENTS |
| | THE CODE REFERENCES GIVE ADDITIONAL INFO |
| | TELEPHONE: (561) 805 6652 ROBERT BROWN |
| | E-MAIL: [email protected] |