Plan Review Notes
Plan Review Notes For Permit 17051086
Permit Number 17051086
Review Stop B
Sequence Number 1
Notes
Date Text
2017-05-25 08:53:32RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- ACCORDING TO THE PALM BEACH COUNTY PROPERTY
 APPRAISER THE VALUE OF THE HOUSE IS MORE THAN
 $3000.000. NEED TO SHOW COMPLIANCE WITH THE ROOF TO
 WALL CONNECTIONS AS REQUIRED BY SEC. 708.8 FBC-EXISTING
 BUILDING, 5TH EDITION (2014).
  
 2- FLAT ROOF NOA 13-0514.10 SUBMITTED: THE SELECTED
 ASSEMBLY IS FOR AN INSULATED FLAT ROOF ASSEMBLY WITH
 -60PSF DESIGN PRESSURES. SEE PAGE 19 OF 26 OF NOA
 SUBMITTED. NEED TO PROVIDE SIGNED AND SEALED RAS 117
 CALCULATIONS AS REQUIRED BY GENERAL LIMITATION #7 ON
 LAST PAGE OF NOA SUBMITTED. PROVIDE 2 SIGNED AND SEALED
 COPIES.
 NEED THE CALCULATIONS TO MEET THE DESIGN PRESSURES
 REQUIRED BY SEC. R301.1 FBC-RESIDENTIAL FOR ALL ROOF
 ZONES.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]