| Plan Review Notes For Permit 17051075 |
| Permit Number |
17051075 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2017-08-17 18:23:55 | RESIDENTIAL (R3) RE-ROOF THIRD BUILDING REVIEW | | | CHECKLIST. | | | CODE: FBC 5TH EDITION (2014). | | | | | | 1- THE PROPOSED ROOF WORK FOR THE FLAT ROOF IS TO | | | RECOVER THE DECK. GENERAL LIMITATION #5 OF RECOVER DECK | | | NOA 13-1022.13 SUBMITTED REQUIRES A FASTENER WITHDRAWAL | | | TEST TAS 105. TEST NEEDS TO BE PERFORMED. PROVIDE 2 | | | COPIES OF THE SIGNED AND SEALED TEST. NOTE: IF THE | | | TESTED FASTENER VALUE IS LESS THAN 275 LBF, THEN | | | INSULATION ATTACHMENT SHALL NOT BE ACCEPTABLE. SEE | | | GENERAL LIMITATION #5 ON LAST PAGE OF NOA. | | | | | | 2- ENGINEER TO REVISE THE RAS 117 CALCULATIONS | | | SUBMITTED: | | | THE FASTENER SPACING FOR THE FIELD AREA DOESN'T MATCH | | | THE FASTENER SPACING SHOWN ON THE NOA SUBMITTED. REVISE | | | AS REQUIRED BY SEC. 8.1 RAS 117. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] |
|