2017-08-17 18:23:55RESIDENTIAL (R3) RE-ROOF THIRD BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 1- THE PROPOSED ROOF WORK FOR THE FLAT ROOF IS TO
 RECOVER THE DECK. GENERAL LIMITATION #5 OF RECOVER DECK
 NOA 13-1022.13 SUBMITTED REQUIRES A FASTENER WITHDRAWAL
 TEST TAS 105. TEST NEEDS TO BE PERFORMED. PROVIDE 2
 COPIES OF THE SIGNED AND SEALED TEST. NOTE: IF THE
 TESTED FASTENER VALUE IS LESS THAN 275 LBF, THEN
 INSULATION ATTACHMENT SHALL NOT BE ACCEPTABLE. SEE
 GENERAL LIMITATION #5 ON LAST PAGE OF NOA.
  
 2- ENGINEER TO REVISE THE RAS 117 CALCULATIONS
 SUBMITTED:
 THE FASTENER SPACING FOR THE FIELD AREA DOESN'T MATCH
 THE FASTENER SPACING SHOWN ON THE NOA SUBMITTED. REVISE
 AS REQUIRED BY SEC. 8.1 RAS 117.
  