| Plan Review Notes For Permit 17051075 |
| Permit Number |
17051075 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2017-08-07 13:10:17 | | | | 08/07/17 MET WITH CONTRACTOR. HE SAID THE FLAT ROOF IS | | | A ROOF OVER. I TOLD HIM HE NEEDS A PRODUCT APPROVAL FOR | | | ROOFOVER APPLICATION AND ENGINEERING NEEDS TO BE | | | REVISED TO MATCH NEW PRODUCT APPROVAL. TOLD HIM TO | | | REVIEW THE LIMITATIONS ON THE ROOF OVER PRODUCT | | | APPROVAL. TESTING MAY BE REQUIRED. JG. | | | | | | | | | | | | RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW CHECKLIST. | | | CODE: FBC 5TH EDITION (2014). | | | | | | 1- ENGINEER TO REVISE THE RAS 117 CALCULATIONS | | | SUBMITTED: | | | (A) SPECIFIC ROOFING ASSEMBLY TO BE INSTALLED IS NOT | | | CLEAR. THE SYSTEM TYPE SPECIFIED BY THE ENGINEER IS: "A | | | PAGE 6,7". THIS IS AN INSULATED SYSTEM. IT DOESN'T | | | MATCH THE SYSTEM TYPE HIGHLIGHTED BY THE ROOFING | | | CONTRACTOR. ROOFING CONTRACTOR HIGHLIGHTED A | | | NON-INSULATED SYSTEM TYPE E ON PAGE 14 AND 15 OF 16. | | | COORDINATE WITH ROOFING CONTRACTOR EXACT SYSTEM TO BE | | | INSTALLED AND REVISE AS REQUIRED. SEC. 107.2.1 CITY | | | AMENDMENTS. | | | | | | (B) SCOPE OF WORK IS NOT CLEAR. THIS IS NOT A "RECOVER" | | | ROOF PROJECT. THIS IS A RE-ROOF PROJECT. SEE PRODUCT | | | APPROVAL SUBMITTED AND REVISE AS REQUIRED. SEC. 107.2.1 | | | CITY AMENDMENTS. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] |
|