| Notes |
| Date |
Text |
| 2017-07-12 07:51:09 | PLAN | | | REVIEW COMMENTS | | | | | | 3RD REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE TESTS THAT WERE SUBMITTED DO NOT MATCH THE SITE | | | CONDITIONS. THE SITE HAS A 7" THICK SLAB AND THE TESTS | | | WERE DONE ON AN 8" THICK SLAB. THERE ARE AREAS THAT DO | | | NOT NOT HAVE A SUSPENDED CEILING AND THE TESTS WERE | | | DONE WITH A SUSPENDED CEILING. FBC 107.2.1 |
|