| Plan Review Notes For Permit 17051039 |
| Permit Number |
17051039 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2017-06-30 17:16:19 | PLAN | | | REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) SUBMIT TWO COPIES OF THE TEST REPORTS OF THE FLAME | | | SPREAD FOR THE SOUND UNDERLAYMENT. FBC 603.1 FLAME | | | SPREAD - ASTM E 84-09 | | | | | | 2) PROVIDE A DESCRIPTION OF EXISTING SITE CONDITIONS: | | | (A) THICKNESS OF SLAB (B) FLOOR/CEILING ASSEMBLY BELOW | | | (EXPOSED CONCRETE, SUSPENDED GYPSUM OR ACOUSTICAL ). | | | THE TEST REPORTS FOR THE SAM 90 SOUND UNDERLAYMENT WERE | | | DONE ON AN 8 INCH CONCRETE FLOOR ASSEMBLY WITH A | | | SUSPENDED GYPSUM BOARD CEILING GRID SYSTEM AND 3.5 INCH | | | UNFACED BATT INSULATION LAID OVER THE GRID SYSTEM. THIS | | | IS NOT THE SITE CONDITION FOR YOUR PROJECT. THE KITCHEN | | | AND BATH AREAS HAVE SUSPENDED CEILINGS WITHOUT THE BATT | | | INSULATION AND THE OTHER AREAS HAVE THE EXPOSED FLOOR | | | SLAB. FBC 107.2.1 | | | | | | |
|