2017-05-26 10:08:581ST REVIEW FBC-2014 BUILDING
 PERMIT #17051038
 5/26/17
  
 RESULTS: DENIED.
  
 1) PLEASE CORRECT THE DESCRIPTION OF WORK ON THE PERMIT
 APPLICATION SO THAT IT READS TILE INSTEAD OF SHINGLES.
  
 2) SUBMIT A COMPLETE FL. PRODUCT APPROVAL FOR THE TILE
 THAT INCLUDES THE COVER SHEET SHOWING THE 2014
 APPROVAL.
  
 3) IN ACCORDANCE WITH SECTION 708.8 FBC-14 EXISTING
 BUILDING CODE, ROOF TO WALL CONNECTIONS SHALL BE
 IMPROVED AS REQUIRED BY SECTION 708.8.1. PLEASE PROVIDE
 AN ENGINEERED DESIGN THAT INCLUDES UPLIFT CAPACITIES
 AND ANCHORING AND STRAPPING DETAILS. AS AN ALTERNATIVE
 TO AN ENGINEERED DESIGN, THE PRESCRIPTIVE RETROFIT
 SOLUTIONS PROVIDED IN SECTIONS 708.8.1.1 THROUGH
 708.8.1.7
  
 SHALL BE ACCEPTED AS MEETING THE MANDATED ROOF-TO-WALL
 RETROFIT REQUIREMENTS.
  
 EXCEPTIONS:
  
 1. WHERE IT CAN BE DEMONSTRATED (BY CODE ADOPTION DATE
 DOCUMENTATION AND PERMIT ISSUANCE DATE) THAT
 ROOF-TO-WALL CONNECTIONS AND/OR ROOF-TO FOUNDATION
 CONTINUOUS LOAD PATH REQUIREMENTS WERE REQUIRED AT THE
 TIME OF ORIGINAL CONSTRUCTION.
  
 2. ROOF-TO-WALL CONNECTIONS SHALL NOT BE REQUIRED
 UNLESS EVALUATION AND INSTALLATION OF CONNECTIONS AT
 GABLE ENDS OR ALL CORNERS CAN BE COMPLETED FOR 15
 PERCENT OF THE COST OF ROOF REPLACEMENT.
  
 CHRISTOPHER L. COLE
 STANDARD PLANS EXAMINER