| 2017-05-26 14:17:58 | BUILDING PLAN REVIEW |
| | NORTON MUSEUM |
| | W. P. B. SUBMITTAL: 17051037 ROOFING SUBMITTALS |
| | W. P. B. PERMIT: 16050912 BUILDING PERMIT |
| | ADD: 1451 S. OLIVE AVE. |
| | CONT: GILBANE |
| | TEL: 561-236-7052 |
| | E-MAIL: [email protected] MICHAEL IZZO |
| | E-MAIL: [email protected] MICHAEL J BEAUMIER |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 1ST REVIEW |
| | DATE: FRI. MAY 26/ 2017 |
| | ACTION: DENIED |
| | |
| | 1) PLEASE NOTE OF THE DIFFERENT ROOFING SUBMITTALS NO |
| | ROOFING PRODUCT APPROVALS WAS SUBMITTED FOR ANY OF THE |
| | PRODUCTS SUBMITTED. |
| | 2014 FBC-B , 1609.6.4.4.1 COMPONENTS & CLADDING. |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE |
| | CODE 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31) |
| | SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT |
| | WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP |
| | VENTILATORS |
| | |
| | 2) SUBMITTAL CROWTHER UNDERLAYMENT POLYGLASS MTS 60 MIL |
| | UNDERLAYMENT WAS NOT APPROVED / RESUBMIT. WHY SUBMITTED |
| | TO THE BUILDING DEPARTMENT WHEN NOT APPROVED. FBC |
| | 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE |
| | REGULATED BY THE DCA RULE 9N-03 SHALL BE REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| | SUBMITTAL FOR JURISDICTIONAL APPROVAL. FL 61G1-23.015 |
| | (2) THE ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND |
| | REVIEWING ALL PROJECT DATA, REPORTS, SHOP DRAWINGS |
| | ETC.. |
| | |
| | 3) FOR EACH OF THE ROOFING PRODUCT APPROVALS PLEASE |
| | IDENTIFY THE TYPE OF ROOF DECK , ROOF TOP INSULATION, |
| | IF ENHANCED FASTENING IS REQUIRED, IF THE PRODUCT |
| | APPROVAL REQUIRES ENGINEERING FOR THE ENHANCED |
| | FASTENING SCHEDULE. SEE LIMITATIONS OF THE PRODUCT |
| | APPROVAL. : FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY |
| | ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES |
| | FOR ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL |
| | LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED FOR ROOF |
| | ZONES 2 & 3. FASTENER DENSITIES SHALL BE INCREASED FOR |
| | BOTH INSULATION & THE BASE SHEET AS CALCULATED IN |
| | COMPLIANCE WITH ROOFING APPLICATION STANDARDS RAS 117. |
| | CALCULATION PREPARED, SIGNED AND SEALED BY A FLORIDA |
| | REGISTERED PROFESSIONAL ENGINEER OR REGISTERED |
| | ARCHITECT. |
| | |
| | 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | THIS REVIEW CYCLE A THOROUGH REVIEW COULD NOT BE |
| | COMPLETED AND ADDITIONAL AND OR NEW COMMENTS MAY OCCUR |
| | ON SUBSEQUENT REVIEWS. |
| | |
| | JAMES A. WITMER BN, PX, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |