Plan Review Notes
Plan Review Notes For Permit 17051021
Permit Number 17051021
Review Stop B
Sequence Number 1
Notes
Date Text
2017-05-26 09:32:18PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 FBC 107.2.1
  
 1) SUBMIT DOCUMENTS FROM THE PBC HEALTH DEPARTMENT AS
 REQUESTED BY THE PLUMBING COMMENTS. FAC 64E-9
  
 2) PROVIDE A LETTER FROM THE CONDO OWNERS ASSOCIATION
 EXPLAINING WHY THE TWO POOLS ARE TO BE REMOVED AND WHAT
 IS THE INTENDED USE OF THE AREA AFTER THE POOLS ARE
 FILLED.
  
 3) PROVIDE A FULL DETAILED SCOPE OF WORK AND SPECIFY IF
 THE EXISTING POOL CABANA IS TO REMAIN OR WILL BE
 DEMOLISHED ON THE PLANS.
  
 4) THE POOL COPING, CONCRETE GUNITE, REINFORCING STEEL,
 TILES, COPING AND DECKING MATERIALS ARE REQUIRED TO BE
 REMOVED FROM THE SITE AND DISPOSED OF PROPERLY, THEY
 CAN NOT BE USED TO FILL THE POOL.
  
 5) REMOVE A TWO FOOT SQUARE SECTION OF CONCRETE GUNITE
 AT THE BOTTOM OF THE POOL AT THE LOWEST POINT IN THE
 DEEP END AND ANOTHER TWO FOOT SQUARE HOLE IN THE
 SHALLOW END.
  
 6) REMOVE ALL ELECTRICAL CONDUCTORS SERVING THE
 ABANDONED POOL FROM THE ELECTRICAL PANEL AND REMOVE OR
 CAP THE VACATED CONDUITS. (ELECTRICAL PERMIT REQUIRED)
  
 7) REMOVE AND CAP ANY GAS LINES SERVICING THE POOL
 HEATER OR SIMILAR ABANDONED GAS FIRED EQUIPMENT. (GAS
 PERMIT REQUIRED)
  
 8) REMOVE ALL ACCESSORIES, INCLUDING LADDERS, SLIDES
 AND DIVING BOARDS.
  
 9) AFTER INITIAL INSPECTION, FILL THE POOL WITH GRAVEL,
 OR SAND. DEMOLITION MATERIALS OR ROCKS OVER 3/4 INCHES
 IN DIAMETER MAY NOT BE USED FOR BACKFILL.
  
 10) BACKFILL SHOULD BE PERFORMED IN LIFTS NOT TO EXCEED
 EIGHT (8) INCH LAYERS AND COMPACTED TO 90%.
  
 11) INSPECTIONS
 A MINIMUM OF TWO INSPECTIONS ARE REQUIRED AS FOLLOWS:
 1. IN PROGRESS DEMOLITION INSPECTION TO BE PERFORMED
 AFTER THE DEMOLITION AND REMOVAL OF ELECTRICAL AND GAS
 LINES BUT PRIOR TO BACK FILL.
 2. FINAL TO BE PERFORMED AFTER THE POOL IS BACKFILLED
 AND PROPERLY GRADED.
  
 IMPORTANT NOTE
 ALLOWING THE POOL SHELL TO REMAIN MAY RESULT IN
 DIFFERENTIAL SETTLEMENT AND THEREFORE THE POOL AREA MAY
 NOT BE USED FOR THE CONSTRUCTION OF FUTURE STRUCTURES.
 TO INSURE THAT THE SOIL IS SUITABLE FOR FUTURE
 CONSTRUCTION, A REPORT FROM A GEOTECHNICAL ENGINEER
 MUST BE PROVIDED AT THE TIME OF PERMIT SUBMITTAL. THAT
 REPORT SHALL IDENTIFY ANY SPECIFIC REMOVAL AND
 COMPACTION REQUIREMENTS AND SHALL BE NOTED ON THE
 SUBMITTED PLANS.
  
 12) SUBMIT A COPY OF THE SIGNED CONTRACT WITH THE CONDO
 ASSOCIATION TO VERY THE VALUE OF THE WORK. FBC 109.3
  
  
  
  