| 2017-06-12 13:11:46 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | |
| | |
| | 1) SHEET A 1.1 - THERE IS A NOTE THAT WAS NOT SUBMITTED |
| | WITH THE ORIGINAL, INDICATING A NEW WOOD FINISH APPLIED |
| | TO THE CEILING. |
| | |
| | PER NFPA 101, CHAPTER 39, EXISTING BUSINESS |
| | OCCUPANCIES, |
| | |
| | |
| | 39.3.3.2 INTERIOR WALL AND CEILING FINISH. |
| | 39.3.3.2.1 INTERIOR WALL AND CEILING FINISH MATERIALS |
| | COMPLYING WITH SECTION 10.2 SHALL BE CLASS A OR CLASS B |
| | IN EXITS AND IN EXIT ACCESS CORRIDORS. |
| | 39.3.3.2.2 INTERIOR WALL AND CEILING FINISHES SHALL BE |
| | CLASS A, CLASS B, OR CLASS C IN AREAS OTHER THAN THOSE |
| | SPECIFIED IN 39.3.3.2.1. |
| | |
| | |
| | 10.2* INTERIOR FINISH. |
| | 10.2.1* GENERAL. |
| | 10.2.1.1 CLASSIFICATION OF INTERIOR FINISH MATERIALS |
| | SHALL BE IN ACCORDANCE WITH TESTS MADE UNDER CONDITIONS |
| | SIMULATING ACTUAL INSTALLATIONS, PROVIDED THAT THE |
| | AUTHORITY HAVING JURISDICTION IS PERMITTED TO ESTABLISH |
| | THE CLASSIFICATION OF ANY MATERIAL ON WHICH |
| | CLASSIFICATION BY A STANDARD TEST IS NOT AVAILABLE, |
| | UNLESS OTHERWISE PROVIDED IN 10.2.1.2 OR 10.2.1.3. |
| | 10.2.1.2 MATERIALS APPLIED DIRECTLY TO THE SURFACE OF |
| | WALLS AND CEILINGS IN A TOTAL THICKNESS OF LESS THAN |
| | 1?28 IN. (0.9 MM) SHALL NOT BE CONSIDERED INTERIOR |
| | FINISH AND SHALL BE EXEMPT FROM TESTS SIMULATING ACTUAL |
| | INSTALLATION IF THEY MEET THE REQUIREMENTS OF CLASS A |
| | INTERIOR WALL OR CEILING FINISH WHEN TESTED IN |
| | ACCORDANCE WITH 10.2.3 USING FIBER CEMENT BOARD AS THE |
| | SUBSTRATE MATERIAL. |
| | 10.2.1.3 APPROVED EXISTING INSTALLATIONS OF MATERIALS |
| | APPLIED DIRECTLY TO THE SURFACE OF WALLS AND CEILINGS |
| | IN A TOTAL THICKNESS OF LESS THAN 1?28 IN. (0.9 MM) |
| | SHALL BE PERMITTED TO REMAIN IN USE, AND THE PROVISIONS |
| | OF 10.2.2 THROUGH 10.2.3.7.2 SHALL NOT APPLY. |
| | |
| | |
| | PLEASE PROVIDE THE APPLICABLE MANUFACTURES SPEC SHEETS |
| | AND AN APPLICABLE NOTE OF COMPLIANCE WITH THE |
| | REQUIREMENT ON THE PLAN SHEET. |
| | |
| | |
| | |
| | |
| | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |