2017-06-13 08:27:25FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
  
  
 C405.2 LIGHTING CONTROLS (MANDATORY).
 LIGHTING SYSTEMS SHALL BE PROVIDED WITH CONTROLS AS
 SPECIFIED IN SECTIONS C405.2.1, C405.2.2, C405.2.3 AND
 C405.2.4.
  
 C405.2.2.2 OCCUPANCY SENSORS.
 OCCUPANCY SENSORS SHALL BE INSTALLED IN ALL CLASSROOMS,
 CONFERENCE/MEETING ROOMS, EMPLOYEE LUNCH AND BREAK
 ROOMS,
 PRIVATE OFFICES, RESTROOMS, STORAGE ROOMS AND
 JANITORIAL CLOSETS, AND OTHER SPACES 300 SQUARE FEET
 (28 M2) OR LESS ENCLOSED
 BY FLOOR-TO-CEILING HEIGHT PARTITIONS. THESE AUTOMATIC
 CONTROL DEVICES SHALL BE INSTALLED TO AUTOMATICALLY
 TURN OFF LIGHTS WITHIN
 30 MINUTES OF ALL OCCUPANTS LEAVING THE SPACE, AND
 SHALL EITHER BE MANUAL ON OR SHALL BE CONTROLLED TO
 AUTOMATICALLY TURN THE
 LIGHTING ON TO NOT MORE THAN 50 PERCENT POWER.
  
 EXCEPTION: FULL AUTOMATIC-ON CONTROLS SHALL BE
 PERMITTED TO CONTROL LIGHTING IN PUBLIC CORRIDORS,
 STAIRWAYS, RESTROOMS,
 PRIMARY BUILDING ENTRANCE AREAS AND LOBBIES, AND AREAS
 WHERE MANUAL-ON OPERATION WOULD ENDANGER THE SAFETY OR
 SECURITY
 OF THE ROOM OR BUILDING OCCUPANTS.
  
 E3706.2 PANELBOARD CIRCUIT IDENTIFICATION.
 ALL CIRCUITS AND CIRCUIT MODIFICATIONS SHALL BE LEGIBLY
 IDENTIFIED AS TO THEIR CLEAR, EVIDENT, AND SPECIFIC
 PURPOSE OR USE.
 THE IDENTIFICATION SHALL INCLUDE SUFFICIENT DETAIL TO
 ALLOW EACH CIRCUIT TO BE DISTINGUISHED FROM ALL OTHERS.
 SPARE POSITIONS
 THAT CONTAIN UNUSED OVERCURRENT DEVICES OR SWITCHES
 SHALL BE DESCRIBED ACCORDINGLY. THE IDENTIFICATION
 SHALL BE INCLUDED
 IN A CIRCUIT DIRECTORY LOCATED ON THE FACE OF THE
 PANELBOARD ENCLOSURE OR INSIDE THE PANEL DOOR. CIRCUITS
 SHALL NOT BE DESCRIBED
 IN A MANNER THAT DEPENDS ON TRANSIENT CONDITIONS OF
 OCCUPANCY.
  
 408.6 CIRCUIT DIRECTORY OR CIRCUIT IDENTIFICATION.
 EVERY CIRCUIT AND CIRCUIT MODIFICATION SHALL BE LEGIBLY
 IDENTIFIED AS TO
 ITS CLEAR, EVIDENT, AND SPECIFIC PURPOSE OR USE. THE
 IDENTIFICATION SHALL INCLUDE AN APPROVED DEGREE OF
 DETAIL THAT ALLOWS
 EACH CIRCUIT TO BE DISTINGUISHED FROM ALL OTHERS. SPARE
 POSITIONS THAT CONTAIN UNUSED OVERCURRENT DEVICES OR
 SWITCHES SHALL BE
 DESCRIBED ACCORDINGLY. THE IDENTIFICATION SHALL BE
 INCLUDED IN A CIRCUIT DIRECTORY THAT IS LOCATED ON THE
 FACE OR INSIDE OF THE
 PANEL DOOR IN THE CASE OF A PANELBOARD AND AT EACH
 SWITCH OR CIRCUIT BREAKER IN A SWITCHBOARD OR
 SWITCHGEAR. NO CIRCUIT SHALL
 BE DESCRIBED IN A MANNER THAT DEPENDS ON TRANSIENT
 CONDITIONS OF OCCUPANCY NEC 2011