| 2017-06-13 08:27:25 | FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED |
| | NFPA 70 2011 EDITION |
| | |
| | JAKE LEAHY |
| | ELECTRICAL PLANS EXAMINER II |
| | 561-805-6713 |
| | [email protected] |
| | |
| | |
| | |
| | C405.2 LIGHTING CONTROLS (MANDATORY). |
| | LIGHTING SYSTEMS SHALL BE PROVIDED WITH CONTROLS AS |
| | SPECIFIED IN SECTIONS C405.2.1, C405.2.2, C405.2.3 AND |
| | C405.2.4. |
| | |
| | C405.2.2.2 OCCUPANCY SENSORS. |
| | OCCUPANCY SENSORS SHALL BE INSTALLED IN ALL CLASSROOMS, |
| | CONFERENCE/MEETING ROOMS, EMPLOYEE LUNCH AND BREAK |
| | ROOMS, |
| | PRIVATE OFFICES, RESTROOMS, STORAGE ROOMS AND |
| | JANITORIAL CLOSETS, AND OTHER SPACES 300 SQUARE FEET |
| | (28 M2) OR LESS ENCLOSED |
| | BY FLOOR-TO-CEILING HEIGHT PARTITIONS. THESE AUTOMATIC |
| | CONTROL DEVICES SHALL BE INSTALLED TO AUTOMATICALLY |
| | TURN OFF LIGHTS WITHIN |
| | 30 MINUTES OF ALL OCCUPANTS LEAVING THE SPACE, AND |
| | SHALL EITHER BE MANUAL ON OR SHALL BE CONTROLLED TO |
| | AUTOMATICALLY TURN THE |
| | LIGHTING ON TO NOT MORE THAN 50 PERCENT POWER. |
| | |
| | EXCEPTION: FULL AUTOMATIC-ON CONTROLS SHALL BE |
| | PERMITTED TO CONTROL LIGHTING IN PUBLIC CORRIDORS, |
| | STAIRWAYS, RESTROOMS, |
| | PRIMARY BUILDING ENTRANCE AREAS AND LOBBIES, AND AREAS |
| | WHERE MANUAL-ON OPERATION WOULD ENDANGER THE SAFETY OR |
| | SECURITY |
| | OF THE ROOM OR BUILDING OCCUPANTS. |
| | |
| | E3706.2 PANELBOARD CIRCUIT IDENTIFICATION. |
| | ALL CIRCUITS AND CIRCUIT MODIFICATIONS SHALL BE LEGIBLY |
| | IDENTIFIED AS TO THEIR CLEAR, EVIDENT, AND SPECIFIC |
| | PURPOSE OR USE. |
| | THE IDENTIFICATION SHALL INCLUDE SUFFICIENT DETAIL TO |
| | ALLOW EACH CIRCUIT TO BE DISTINGUISHED FROM ALL OTHERS. |
| | SPARE POSITIONS |
| | THAT CONTAIN UNUSED OVERCURRENT DEVICES OR SWITCHES |
| | SHALL BE DESCRIBED ACCORDINGLY. THE IDENTIFICATION |
| | SHALL BE INCLUDED |
| | IN A CIRCUIT DIRECTORY LOCATED ON THE FACE OF THE |
| | PANELBOARD ENCLOSURE OR INSIDE THE PANEL DOOR. CIRCUITS |
| | SHALL NOT BE DESCRIBED |
| | IN A MANNER THAT DEPENDS ON TRANSIENT CONDITIONS OF |
| | OCCUPANCY. |
| | |
| | 408.6 CIRCUIT DIRECTORY OR CIRCUIT IDENTIFICATION. |
| | EVERY CIRCUIT AND CIRCUIT MODIFICATION SHALL BE LEGIBLY |
| | IDENTIFIED AS TO |
| | ITS CLEAR, EVIDENT, AND SPECIFIC PURPOSE OR USE. THE |
| | IDENTIFICATION SHALL INCLUDE AN APPROVED DEGREE OF |
| | DETAIL THAT ALLOWS |
| | EACH CIRCUIT TO BE DISTINGUISHED FROM ALL OTHERS. SPARE |
| | POSITIONS THAT CONTAIN UNUSED OVERCURRENT DEVICES OR |
| | SWITCHES SHALL BE |
| | DESCRIBED ACCORDINGLY. THE IDENTIFICATION SHALL BE |
| | INCLUDED IN A CIRCUIT DIRECTORY THAT IS LOCATED ON THE |
| | FACE OR INSIDE OF THE |
| | PANEL DOOR IN THE CASE OF A PANELBOARD AND AT EACH |
| | SWITCH OR CIRCUIT BREAKER IN A SWITCHBOARD OR |
| | SWITCHGEAR. NO CIRCUIT SHALL |
| | BE DESCRIBED IN A MANNER THAT DEPENDS ON TRANSIENT |
| | CONDITIONS OF OCCUPANCY NEC 2011 |