| 2017-06-12 09:51:54 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | ACTION: DENIED |
| | |
| | 1. REVISE PLAN TO INCLUDE ALL INFORMATION REQUIRED TO |
| | BE ON THE TITLE BLOCK FOR THE ARCHITECT, FLORIDA |
| | STATUTE 481, FLORIDA ADMINISTRATIVE CODE 61G1-16.004. |
| | |
| | 2. COMMENT FROM FIRST REVIEW, NOT ADDRESSED: |
| | |
| | PLEASE IDENTIFY THE SCOPE OF WORK. THE PERMIT |
| | APPLICATION INDICATES REPAIRS, THIS APPEARS TO BE A |
| | LEVEL II ALTERATION UNDER THE WORK AREA METHOD OF THE |
| | 2014 EXISTING BUILDING CODE. PLEASE DECLARE LEVEL OF |
| | ALTERATION: |
| | |
| | REPAIRS. REPAIRS, AS DEFINED IN CHAPTER 2, INCLUDE THE |
| | PATCHING OR RESTORATION OR REPLACEMENT OF DAMAGED |
| | MATERIALS, ELEMENTS, EQUIPMENT OR FIXTURES FOR THE |
| | PURPOSE OF MAINTAINING SUCH COMPONENTS IN GOOD OR SOUND |
| | CONDITION WITH RESPECT TO EXISTING LOADS OR PERFORMANCE |
| | REQUIREMENTS. |
| | |
| | LEVEL 1 ALTERATIONS INCLUDE THE REMOVAL AND REPLACEMENT |
| | OR THE COVERING OF EXISTING MATERIALS, ELEMENTS, |
| | EQUIPMENT, OR FIXTURES USING NEW MATERIALS, ELEMENTS, |
| | EQUIPMENT, OR FIXTURES THAT SERVE THE SAME PURPOSE. |
| | |
| | LEVEL 2 ALTERATIONS INCLUDE THE RECONFIGURATION OF |
| | SPACE, THE ADDITION OR ELIMINATION OF ANY DOOR OR |
| | WINDOW, THE RECONFIGURATION OR EXTENSION OF ANY SYSTEM, |
| | OR THE INSTALLATION OF ANY ADDITIONAL EQUIPMENT. |
| | |
| | 2ND REVIEW, PROJECT DESCRIPTION IS "REPAIRS." IT IS NOT |
| | CLEAR WHAT IS BEING REPAIRED. |
| | SOME WORK WAS ALREADY DONE WITHOUT PERMIT. THE FIRST |
| | PLAN SUBMITTED SHOWS DEMO OF THE ACOUSTIC CEILING; NEW |
| | PLAN DOES NOT SHOW THIS WORK. |
| | |
| | CONFIRM THAT ALL WORK PROPOSED, INCLUDING WORK DONE |
| | WITHOUT PERMITS, IS INCLUDED ON THE PLAN. |
| | |
| | REVISE PLAN TO SHOW NATURE OF "REPAIRS" OR DECLARE |
| | LEVEL OF ALTERATION. BASED ON THE PLAN SUBMITTED, THIS |
| | APPEARS TO BE A LEVEL 2 ALTERATION; REVISE PLAN |
| | ACCORDINGLY. |
| | |
| | 3. COMMENT FROM FIRST REVIEW, NOT ADDRESSED: |
| | |
| | PLEASE INSPECT BEFORE REMOVAL OF WALL, NOTE ON THE |
| | PLANS WHERE THE DOOR, SIDELIGHTS, DOOR FRAME, AND WALL |
| | SECTION ARE BEING REMOVED THIS IS A NON-BEARING WALL. |
| | 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 4. PLAN REFERENCES EXISTING MARBLE, SHOWS REMOVAL OF |
| | CARPET IN SOME AREAS AS WELL AS INSTALLATION OF TILE. |
| | |
| | SEE FBC A 404.3; REVISE PLAN TO SHOW PROPOSED ELEVATION |
| | CHANGES BETWEEN THE NEW TILE AREAS AND EXISTING AREAS |
| | WHICH WILL NOT BE ALTERED. |
| | |
| | 5. FBC 109, PROVIDE A COPY OF THE CONTRACT FOR THIS |
| | JOB. A COST BREAKDOWN (LABOR, MATERIALS, ETC.) MAY ALSO |
| | BE REQUIRED. VALUE ON APPLICATION IS UNREASONABLY LOW. |
| | |
| | 6. WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |