Plan Review Notes
Plan Review Notes For Permit 17051018
Permit Number 17051018
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2017-05-30 14:12:38THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE IS NO INDICATIONS OF AN EXIT SIGN AT THE
 RECEPTION AREA LEADING TO THE FRONT LOBBY EXIT.
  
 PER NFPA 101, CHAPTER 39, EXISTING BUSINESS
 OCCUPANCIES.
  
 39.2.7 DISCHARGE FROM EXITS. EXIT DISCHARGE SHALL
 COMPLY WITH SECTION 7.7.
  
 39.2.8 ILLUMINATION OF MEANS OF EGRESS. MEANS OF EGRESS
 SHALL BE ILLUMINATED IN ACCORDANCE WITH SECTION 7.8.
  
 39.2.10 MARKING OF MEANS OF EGRESS. MEANS OF EGRESS
 SHALL HAVE SIGNS IN ACCORDANCE WITH SECTION 7.10.
  
 PER NFPA 101, CHAPTER 7, MEANS OF EGRESS.
  
 7.7.3 ARRANGEMENT AND MARKING OF EXIT DISCHARGE.
  
 7.7.3.2 THE EXIT DISCHARGE SHALL BE ARRANGED AND MARKED
 TO MAKE CLEAR THE DIRECTION OF EGRESS TRAVEL FROM THE
 EXIT DISCHARGE TO A PUBLIC WAY.
  
  
 7.8 ILLUMINATION OF MEANS OF EGRESS.
 7.8.1 GENERAL.
 7.8.1.1* ILLUMINATION OF MEANS OF EGRESS SHALL BE
 PROVIDED IN ACCORDANCE WITH SECTION 7.8 FOR EVERY
 BUILDING AND STRUCTURE WHERE REQUIRED IN CHAPTERS 11
 THROUGH 43. FOR THE PURPOSES OF THIS REQUIREMENT, EXIT
 ACCESS SHALL INCLUDE ONLY DESIGNATED STAIRS,AISLES,
 CORRIDORS, RAMPS, ESCALATORS, AND PASSAGEWAYS LEADING
 TO AN EXIT. FOR THE PURPOSES OF THIS REQUIREMENT, EXIT
 DISCHARGE SHALL INCLUDE ONLY DESIGNATED STAIRS, AISLES,
 CORRIDORS, RAMPS, ESCALATORS, WALKWAYS, AND EXIT
 PASSAGEWAYS LEADING TO A PUBLIC WAY.
 7.8.1.2 ILLUMINATION OF MEANS OF EGRESS SHALL BE
 CONTINUOUS DURING THE TIME THAT THE CONDITIONS OF
 OCCUPANCY REQUIRE THAT THE MEANS OF EGRESS BE AVAILABLE
 FOR USE, UNLESS OTHERWISE PROVIDED IN 7.8.1.2.2.
  
 7.10.1.2 EXITS.
 7.10.1.2.1* EXITS, OTHER THAN MAIN EXTERIOR EXIT DOORS
 THAT OBVIOUSLY AND CLEARLY ARE IDENTIFIABLE AS EXITS,
 SHALL BE MARKED BY AN APPROVED SIGN THAT IS READILY
 VISIBLE FROM ANY DIRECTION OF EXIT ACCESS.
 7.10.1.2.2* HORIZONTAL COMPONENTS OF THE EGRESS PATH
 WITHIN AN EXIT ENCLOSURE SHALL BE MARKED BY APPROVED
 EXIT OR DIRECTIONAL EXIT SIGNS WHERE THE CONTINUATION
 OF THE EGRESS PATH IS NOT OBVIOUS. PLEASE ENSURE ONE IS
 EXISTING OR PROVIDE.
  
  
 PLEASE NOTE IF ONE IS EXISTING OR PROVIDE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  