Plan Review Notes
Plan Review Notes For Permit 17050993
Permit Number 17050993
Review Stop G
Sequence Number 2
Notes
Date Text
2017-05-31 06:24:301) THE SUBMITTED FLOOR PLAN SHOWS PE PIPE BEING RUN
 UNDER A COVERED PATIO AND THE BUILDING. THIS IS NOT
 PERMITTED PER THE 2014 FBC-FUEL GAS SECTION 404.17.1.
 PE PIPE SHALL ONLY BE INSTALLED OUTSIDE UNDERGROUND
 2014 FBC-FUEL GAS SEC.404.17.1,
 2) SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR THE DRYER
 THAT IS LOCATED IN THE LAUNDRY ROOM PER THE 2014
 FBC-FUEL GAS CODE SEC.304.1, 614.5 OR 2014 FBC-RES.
 SEC. G 2407.1, G2439.4. 2ND REQUEST.
 3) THE GAS RISER SHOWS THE GALVANIZED DROP TO THE NEW
 DRYER LOCATION AS 3/4 INCH AND ALSO AS 1/2 INCH.
 CLARIFY.
 4) WHAT IS THE LENGTH OF PIPING OF THE 1 INCH RISER AND
 3/4 INCH GALVANIZED PIPE FROM THE METER TO THE
 CONNECTION WITH THE 3/4 INCH PE PIPE? THIS DISTANCE
 SHALL BE INCLUDED IN THE TOTAL DEVELOPED LENGTHAND
 SHALL BE NOTED ON THE PLAN.
 5) THE 1 INCH RISER FROM THE METER IS UNDERSIZED FOR
 THE TOTAL BTU LOAD ON SCHEDULE 40 METALLIC PIPE PER THE
 SUBMITTED TABLE 402.4 (2). THE TOTAL DEVELOPED LENGTH
 TO BE USED FOR SIZING THIS LINE IS 90 FEET SINCE THERE
 IS NO 85 FEET ROW IN THE TABLE. THE MINIMUM SIZE FROM
 THE METER SHALL BE 1 1/4 INCH ON A SYSTEM THAT IS LESS
 THAN 2 PSI WITH A TOTAL BTU LOAD OF 254,000.
 6) SUBMIT TWO COPIES OF THE FLOOR PLAN. WPB AMEND. TO
 FBC SEC. 107.1.
 7) SUBMIT TWO COPIES OF SPECS FOR ALL GAS EQUIPMENT.WPB
 AMEND. TO FBC SEC. 107.1.
  
 I SUGGEST CALLING TO SET UP AN APPOINTMENT TO REVIEW
 THE PLAN REVIEW COMMENTS.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  
  
  
  
  
  
  
  