| 2017-07-28 14:12:19 | CODES IN EFFECT: |
| | FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| | EDITION |
| | NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | |
| | ELECTRICAL REVIEW (2ND REVIEW) COMMENTS: |
| | |
| | 1. PREVIOUS COMMENT #1 NOT ADDRESSED SATISFACTORILY. |
| | RISER DIAGRAM IS NOT COMPLETE, DOES NOT SHOW NEW PANEL |
| | FOR GUEST HOUSE (WHERE IS THIS FED FROM?), DOES NOT |
| | PROVIDE WIRE SIZES AS REQUESTED. PROVIDE AS PREVIOUSLY |
| | REQUESTED: "PROVIDE RISER DIAGRAM SHOWING EXISTING |
| | SERVICE AND ANY NEW WIRING. PROVIDE DETAILS OF WIRE AND |
| | CONDUIT SIZE". NEC 215.5, FBC 107.3.5 |
| | 2. PREVIOUS COMMENT #2 NOT ADDRESSED SATISFACTORILY. |
| | LOAD FOR SERVICE WAS NOT SUPPLIED ON PREVIOUS PERMIT |
| | 17050712. PROVIDE AS PREVIOUSLY REQUESTED: "PROVIDE |
| | LOAD CALCULATION FOR MAIN SERVICE INCLUDING NEW LOADS |
| | TO BE ADDED TO DETERMINE CURRENT SERVICE IS |
| | SUFFICIENT". NEC 220, FBC RE3602.2 |
| | 3. PREVIOUS COMMENT #3 NOT ADDRESSED SATISFACTORILY. |
| | RESPONSE TO COMMENT STATES THAT THE SERVICE WILL BE |
| | MOUNTED ON GUEST HOUSE WHEN BUILT. SHOW LOCATION OF |
| | SERVICE ON PLAN. SHOW LOCATION OF NEW 100 AMP PANEL. BE |
| | ADVISED THAT ANY SEPARATE STRUCTURE IS REQUIRED TO HAVE |
| | A MAIN BREAKER OR DISCONNECT FOR THAT STRUCTURE. THE |
| | RISER DIAGRAM PROVIDED SHOWS THE OTHER PANELS AS MAIN |
| | LUG ONLY PANELS, WHICH WILL NEED TO BE CORRECTED. |
| | PROVIDE AS PREVIOUSLY REQUESTED: "PROVIDE DISCONNECT |
| | FOR ELECTRICAL SERVICE TO NEW BUILDING PER SECTION II |
| | OF THE NEC". NEC 225.30, 225.31, 225.33 |
| | 4. PREVIOUS COMMENT #4 NOT ADDRESSED SATISFACTORILY. |
| | EACH SEPARATE BUILDING OR STRUCTURE MUST HAVE A |
| | GROUNDING ELECTRODE SYSTEM ESTABLISHED AND BONDED |
| | TOGETHER PER NEC 250.32. PROVIDE AS PREVIOUSLY |
| | REQUESTED: "PROVIDE GROUNDING ELECTRODE CONDUCTOR AND |
| | GROUNDING ELECTRODE AT SEPARATE BUILDING WITH |
| | INTERSYSTEM BONDING TERMINATION POINT". NEC 250.32, |
| | 250.64, 250.94, FBC RE3609.3.5 |
| | 5.PREVIOUS COMMENT #5 ADDRESSED, BUT NEEDS CORRECTION. |
| | WATER HEATER IS SHOWN WITH A 30 AMP BREAKER, THIS |
| | SHOULD BE A 25 AMP PER CODE(BASED ON 4500 WATTS). |
| | BATHROOM OUTLETS REQUIRES A DEDICATED 20 AMP CIRCUIT |
| | WITH GFCI PROTECTION(THE RECEPTACLES DO NOT CURRENTLY |
| | SHOW GFCI PROTECTION). THE OUTLETS IN THE STORAGE AREA |
| | REQUIRE GFCI PROTECTION(THE RECEPTACLES DO NOT |
| | CURRENTLY SHOW GFCI PROTECTION).PROVIDE CORRECTION. NEC |
| | 210.8, 210.11, 408.4, 422.13; FBC RE3703.4, RE 3902.1, |
| | RE3902.2 |
| | 6. RISER PROVIDED SHOW 3 LEADS OF 2/0 TO 200 AMP PANEL. |
| | 2/0 IS NOT RATED FOR 200 AMPS. PROVIDE CORRECTION. NEC |
| | 310.15(B)(16); FBC RE3602.2 |
| | 7. PREVIOUS COMMENT #7 NOT ADDRESSED SATISFACTORILY. |
| | RESPONSE STATED THE LIGHT AND FAN LOCATIONS WERE MOVED, |
| | HOWEVER, THEY ARE IS THE SAME LOCATION. PROVIDE AS |
| | PREVIOUSLY REQUESTED: "IT APPEARS FROM SCALING THE |
| | PRINT THAT THERE ARE LIGHT FIXTURES AND CEILING FANS |
| | LOCATED WITHIN THE 5 FEET HORIZONTAL AND 12 FEET HEIGHT |
| | ZONE DESCRIBED IN NEC 680.22. PROVIDE CORRECTION". NEC |
| | 680.22(B), FBC RE4203.4 |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |