Plan Review Notes
Plan Review Notes For Permit 17050988
Permit Number 17050988
Review Stop E
Sequence Number 1
Notes
Date Text
2017-06-06 10:15:27CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS:
  
 1. PROVIDE RISER DIAGRAM SHOWING EXISTING SERVICE AND
 ANY NEW WIRING. PROVIDE DETAILS OF WIRE AND CONDUIT
 SIZE. NEC 215.5, FBC 107.3.5
 2. PROVIDE LOAD CALCULATION FOR MAIN SERVICE INCLUDING
 NEW LOADS TO BE ADDED TO DETERMINE CURRENT SERVICE IS
 SUFFICIENT. NEC 220, FBC RE3602.2
 3. PROVIDE DISCONNECT FOR ELECTRICAL SERVICE TO NEW
 BUILDING PER SECTION II OF THE NEC. NEC 225.30, 225.31,
 225.33
 4. PROVIDE GROUNDING ELECTRODE CONDUCTOR AND GROUNDING
 ELECTRODE AT SEPARATE BUILDING WITH INTERSYSTEM BONDING
 TERMINATION POINT. NEC 250.64, 250.94, FBC RE3609.3.5
 5. PROVIDE PANEL SCHEDULE, INDICATE WIRE AND BREAKER
 SIZE FOR EACH CIRCUIT. INDICATE CIRCUITS THAT ARE TO BE
 AFCI OR GFCI PROTECTED PER CODE. NEC 210.8, 210.12,
 408.4, 680.22, FBC RE3706.2
 6. PROVIDE ELECTRICAL PLAN FOR ADDITION TO MAIN HOUSE
 FOR REVIEW. FBC 107.2.1
 7. IT APPEARS FROM SCALING THE PRINT THAT THERE ARE
 LIGHT FIXTURES AND CEILING FANS LOCATED WITHIN THE 5
 FEET HORIZONTAL AND 12 FEET HEIGHT ZONE DESCRIBED IN
 NEC 680.22. PROVIDE CORRECTION. NEC 680.22(B), FBC
 RE4203.4
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  