| 2017-06-06 10:15:27 | CODES IN EFFECT: |
| | FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| | EDITION |
| | NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | |
| | ELECTRICAL REVIEW COMMENTS: |
| | |
| | 1. PROVIDE RISER DIAGRAM SHOWING EXISTING SERVICE AND |
| | ANY NEW WIRING. PROVIDE DETAILS OF WIRE AND CONDUIT |
| | SIZE. NEC 215.5, FBC 107.3.5 |
| | 2. PROVIDE LOAD CALCULATION FOR MAIN SERVICE INCLUDING |
| | NEW LOADS TO BE ADDED TO DETERMINE CURRENT SERVICE IS |
| | SUFFICIENT. NEC 220, FBC RE3602.2 |
| | 3. PROVIDE DISCONNECT FOR ELECTRICAL SERVICE TO NEW |
| | BUILDING PER SECTION II OF THE NEC. NEC 225.30, 225.31, |
| | 225.33 |
| | 4. PROVIDE GROUNDING ELECTRODE CONDUCTOR AND GROUNDING |
| | ELECTRODE AT SEPARATE BUILDING WITH INTERSYSTEM BONDING |
| | TERMINATION POINT. NEC 250.64, 250.94, FBC RE3609.3.5 |
| | 5. PROVIDE PANEL SCHEDULE, INDICATE WIRE AND BREAKER |
| | SIZE FOR EACH CIRCUIT. INDICATE CIRCUITS THAT ARE TO BE |
| | AFCI OR GFCI PROTECTED PER CODE. NEC 210.8, 210.12, |
| | 408.4, 680.22, FBC RE3706.2 |
| | 6. PROVIDE ELECTRICAL PLAN FOR ADDITION TO MAIN HOUSE |
| | FOR REVIEW. FBC 107.2.1 |
| | 7. IT APPEARS FROM SCALING THE PRINT THAT THERE ARE |
| | LIGHT FIXTURES AND CEILING FANS LOCATED WITHIN THE 5 |
| | FEET HORIZONTAL AND 12 FEET HEIGHT ZONE DESCRIBED IN |
| | NEC 680.22. PROVIDE CORRECTION. NEC 680.22(B), FBC |
| | RE4203.4 |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |