| Plan Review Notes For Permit 17050979 |
| Permit Number |
17050979 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-05-31 14:08:30 | PER NFPA 72 SECTION 24.5.2.2.1 CRITICAL AREAS. CRITICAL | | | AREAS, SUCH AS THE FIRE COMMAND CENTER(S), THE FIRE | | | PUMP ROOM(S), EXIT STAIRS, EXIT PASSAGEWAYS, ELEVATOR | | | LOBBIES, STANDPIPE CABINETS, SPRINKLER SECTIONAL VALVE | | | LOCATIONS, AND OTHER AREAS DEEMED CRITICAL BY THE | | | AUTHORITY HAVING JURISDICTION, SHALL BE PROVIDED WITH | | | 99 PERCENT FLOOR AREA RADIO COVERAGE. GENERAL BUILDING | | | AREAS SHALL BE PROVIDED WITH 90 PERCENT FLOOR AREA | | | RADIO COVERAGE. A MINIMUM INBOUND/OUTBOUND SIGNAL | | | STRENGTH OF -95 DBM SHALL BE PROVIDED THROUGHOUT THE | | | COVERAGE AREA. | | | | | | NEED A #301 AND #302 FIRE INSPECTION. |
|