| Plan Review Notes For Permit 17050943 |
| Permit Number |
17050943 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-05-31 17:57:18 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE PLANS ARE TOO SMALL AND THE PRINT IS ILLEGIBLE. | | | FBC 107.2.1.4 REQUIRES THE PLANS TO BE A MINIMUM 1/8 | | | INCH SCALE. | | | | | | 2) THE PLANS ARE REQUIRED TO HAVE THE ENGINEER'S | | | ORIGINAL HANDWRITTEN SIGNATURE, COPIES OR OTHER | | | FACSMILES ARE NOT ACCEPTABLE. FAC 61G15-23.002 DIGITAL | | | SIGNATURES ARE ONLY ALLOWED FOR ELECTRONICALLY | | | SUBMITTED PLANS. | | | | | | 3) THE VULT WIND SPEED OF 150 MPH IS NOT ADEQUATE FOR | | | THIS LOCATION. GARDEN SHEDS ARE CLASSIFIED AS RISK | | | CATEGORY I STRUCTURES AND THE VULT WINDSPEED IS 155 MPH | | | OR MORE AT THIS LOCATION PER FBC TABLE 1604.5 AND | | | FIGURE 1609C. IF THIS STRUCTURE WILL BE USED AS AN | | | OFFICE THEN IT IS CLASSIFIED AS RISK CATEGORY II AND | | | THE VULT WINDSPEED IS 170 MPH PER FBC TABLE 1604.5 AND | | | FIGURE 1609A. |
|