| Plan Review Notes For Permit 17050942 |
| Permit Number |
17050942 |
|
| Review Stop |
SIGNATURE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-06-09 08:10:23 | ELECTRICAL PLAN HAS NO DIGITAL SIGNATURE. JP 06-09-17 | | 2017-06-09 07:41:01 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. ELECTRICAL SHEET IS NOT SIGNED AND SEALED AS | | | REQUIRED BY FS471, FAC61G15-23. | | | | | | THE ENGINEER'S TITLE BLOCK IS NOT IN COMPLIANCE WITH | | | FS471, FAC61G15-23.002 (CERTIFICATE OF AUTHORIZATION | | | FOR T.E., INC. LACKING). | | | | | | IF ENGINEER DOES NOT HAVE A DIGITAL OR ELECTRONIC | | | SIGNATURE & SEAL, YOU MAY PROVIDE AN ORIGINAL SIGNED | | | AND SEALED PAPER DOCUMENT. | | | | | | 2. THE DBPR WEBSITE (MYFLORIDALICENSE.COM) DOES NOT | | | REFLECT THAT ELECTRICAL ENGINEER HAS COMPLETED THE | | | ADVANCED FLORIDA BUILDING CODE COURSE REQUIRED BY | | | FS471.0195. PLEASE SEND EVIDENCE THAT THE COURSE WAS | | | COMPLETED (DUE BY JUNE 30, 2016) TO FBPE AND REQUEST | | | THAT YOUR RECORD BE UPDATED. | | | | | | 3. SEE BUILDING COMMENT REGARDING ARCHITECT'S TITLE | | | BLOCK. REVISE ALL RESUBMITTED SHEETS, FAC61G1-16.004. | | | | | | ARCHITECT'S SIGNATURE AND SEAL ARE OK; NEW SHEETS | | | SUBMITTED FOR REVIEW CYCLE #3 NEED TO BE VERIFIED. | | | | | | |
|