Plan Review Notes
Plan Review Notes For Permit 17050942
Permit Number 17050942
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2017-06-05 09:50:54THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) SHEET A 501 - THE DRAWING INDICATES THAT WHEN THE
 PROPOSED GARAGE DOOR IS OPEN, IT MAY POSE AS AN
 OBSTRUCTION TO THE EXISTING FIRE SPRINKLER HEAD
 LOCATIONS.
  
 PLEASE REVIEW AND PROVIDE A REVIEW FROM A FIRE
 SPRINKLER CONTRACTOR THAT NO OBSTRUCTION WILL OCCUR OR
 PROVIDE A NOTE INDICATING THAT THE FIRE SPRINKLER HEAD
 LOCATION WILL BE MODIFIED TO PROVIDE CODE COVERAGE.
  
  
  
  
 2) SHEET E 1 - THOUGH IT MAY BE EXISTING, THERE ARE NO
 INDICATIONS THAT THE EXIT SIGNS AND EMERGENCY LIGHTS
 ARE EXISTING AND/OR THAT THEY WILL BE INSTALLED WITH
 THE PROPOSED PROJECT.
  
 PROVIDE DRAWING INDICATIONS OR AN APPLICABLE NOTE THAT
 THEY ARE EXISTING.
  
  
  
 PETER LEDUC
 FIRE MARSHAL