| Plan Review Notes For Permit 17050942 |
| Permit Number |
17050942 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-06-05 09:50:54 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | | | | 1) SHEET A 501 - THE DRAWING INDICATES THAT WHEN THE | | | PROPOSED GARAGE DOOR IS OPEN, IT MAY POSE AS AN | | | OBSTRUCTION TO THE EXISTING FIRE SPRINKLER HEAD | | | LOCATIONS. | | | | | | PLEASE REVIEW AND PROVIDE A REVIEW FROM A FIRE | | | SPRINKLER CONTRACTOR THAT NO OBSTRUCTION WILL OCCUR OR | | | PROVIDE A NOTE INDICATING THAT THE FIRE SPRINKLER HEAD | | | LOCATION WILL BE MODIFIED TO PROVIDE CODE COVERAGE. | | | | | | | | | | | | | | | 2) SHEET E 1 - THOUGH IT MAY BE EXISTING, THERE ARE NO | | | INDICATIONS THAT THE EXIT SIGNS AND EMERGENCY LIGHTS | | | ARE EXISTING AND/OR THAT THEY WILL BE INSTALLED WITH | | | THE PROPOSED PROJECT. | | | | | | PROVIDE DRAWING INDICATIONS OR AN APPLICABLE NOTE THAT | | | THEY ARE EXISTING. | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|