2017-05-25 15:40:19FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 FBC- 107.3.5.3 ? ELECTRIC SERVICE RISER . COMPLETE LOAD
 CALCULATIONS, PANEL SCHEDULES .
  
 408.4 FIELD IDENTIFICATION REQUIRED.
 (A) CIRCUIT DIRECTORY OR CIRCUIT IDENTIFICATION. EVERY
 CIRCUIT AND CIRCUIT MODIFICATION SHALL BE LEGIBLY
 IDENTIFIED AS
 TO ITS CLEAR, EVIDENT, AND SPECIFIC PURPOSE OR USE. THE
 IDENTIFICATION SHALL INCLUDE AN APPROVED DEGREE OF
 DETAIL THAT
 ALLOWS EACH CIRCUIT TO BE DISTINGUISHED FROM ALL
 OTHERS. SPARE POSITIONS THAT CONTAIN UNUSED OVERCUN'ENT
 DEVICES OR
 SWITCHES SHALL BE DESCRIBED ACCORDINGLY. THE
 IDENTIFICATION SHALL BE INCLUDED IN A CIRCUIT DIRECTORY
 THAT IS LOCATED ON THE
 FACE OR INSIDE OF THE PANEL DOOR IN THE CASE OF A
 PANELBOARD AND AT EACH SWITCH OR CIRCUIT BREAKER IN A
 SWITCHBOARD OR
 SWITCHGEAR. NO CIRCUIT SHALL BE DESCRIBED IN A MANNER
 THAT DEPENDS ON TRANSIENT CONDITIONS OF OCCUPANCY.