| Plan Review Notes For Permit 17050921 |
| Permit Number |
17050921 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-05-25 15:40:19 | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70 2011 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | FBC- 107.3.5.3 ? ELECTRIC SERVICE RISER . COMPLETE LOAD | | | CALCULATIONS, PANEL SCHEDULES . | | | | | | 408.4 FIELD IDENTIFICATION REQUIRED. | | | (A) CIRCUIT DIRECTORY OR CIRCUIT IDENTIFICATION. EVERY | | | CIRCUIT AND CIRCUIT MODIFICATION SHALL BE LEGIBLY | | | IDENTIFIED AS | | | TO ITS CLEAR, EVIDENT, AND SPECIFIC PURPOSE OR USE. THE | | | IDENTIFICATION SHALL INCLUDE AN APPROVED DEGREE OF | | | DETAIL THAT | | | ALLOWS EACH CIRCUIT TO BE DISTINGUISHED FROM ALL | | | OTHERS. SPARE POSITIONS THAT CONTAIN UNUSED OVERCUN'ENT | | | DEVICES OR | | | SWITCHES SHALL BE DESCRIBED ACCORDINGLY. THE | | | IDENTIFICATION SHALL BE INCLUDED IN A CIRCUIT DIRECTORY | | | THAT IS LOCATED ON THE | | | FACE OR INSIDE OF THE PANEL DOOR IN THE CASE OF A | | | PANELBOARD AND AT EACH SWITCH OR CIRCUIT BREAKER IN A | | | SWITCHBOARD OR | | | SWITCHGEAR. NO CIRCUIT SHALL BE DESCRIBED IN A MANNER | | | THAT DEPENDS ON TRANSIENT CONDITIONS OF OCCUPANCY. |
|