| 2017-07-20 11:17:18 | 2014 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 17050881 |
| | ADD: 805 19TH ST. |
| | CONT: M. J. EBERSBACH CONSTRUCTION |
| | TEL: 561-271-0136 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 3RD REVIEW |
| | DATE: THURS. JULY 20/ 2017 |
| | ACTION: DENIED |
| | |
| | 1) BUILDING PROVISO: CHANGE OUT OF ALL WINDOWS FOR 1ST |
| | & 2ND FLOOR. EXCEPTION TO SECTION 704.1 OF THE 2014 |
| | EXISTING BUILDING CODE AN ALLOWABLE 5 PERCENT REDUCTION |
| | IN THE CLEAR OPENING DIMENSIONS OF THE REPLACEMENT |
| | WINDOW. THE CONTRACTOR HAS SUBMITTED PICTURES OF |
| | EXISTING SINGLE HUNG WINDOWS IN THE EXISTING OPENING. |
| | |
| | 2) 2ND REQUEST. 107.2.4 EXTERIOR WALL ENVELOPE. FOR ALL |
| | PRODUCTS WITH GLAZING, PLEASE IDENTIFY THE OPENING |
| | WIDTH & HEIGHT, TYPE OF GLAZING, MULLION INFORMATION IF |
| | REQUIRED, ATTACHMENTS AND ASSOCIATE PRESSURES FOR EACH |
| | OPENING SIZE. INSTALLATION. WINDOWS AND DOORS SHALL BE |
| | INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURERS |
| | INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE |
| | PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED |
| | BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS. |
| | THE CONSTRUCTION DOCUMENTS SHALL INCLUDE MANUFACTURERS |
| | INSTALLATION INSTRUCTIONS THAT PROVIDE SUPPORTING |
| | DOCUMENTATION THAT THE PROPOSED PENETRATION AND OPENING |
| | DETAILS DESCRIBED IN THE CONSTRUCTION DOCUMENTS |
| | MAINTAIN THE WEATHER RESISTANCE OF THE EXTERIOR WALL |
| | ENVELOPE. |
| | |
| | 3-4) COMPLIED. |
| | |
| | 5) NEW COMMENT. SHEET # 2 SHOWS NEW AIR CONDENSERS ON |
| | CONCRETE PADS PLEASE PROVIDE ENGINEERING HOW THESE |
| | UNITS WILL BE ANCHORED TO THE CONCRETE PAD. PROVIDE |
| | LATERAL FORCE RESISTING SYSTEM. 2014 FBC-B 1604.4 |
| | ANALYSIS. SEE MECH. PLAN REVIEW AS WELL. |
| | |
| | 6) NEW COMMENT. SUBMITTED DOOR AND MULLION PRODUCT |
| | APPROVAL WITH THE DESIGNER OF RECORD REVIEW. THIS |
| | REVIEW I COULD FIND NO WINDOW PRODUCT APPROVAL FOR ANY |
| | TYPE OF WINDOW. THE WINDOW SCHEDULE ON SHEET A.2 DOES |
| | INDICATE ALL OF THE NEW WINDOWS ARE TO BE SINGLE HUNG |
| | WINDOWS. PLEASE COMPLY WITH 2014 FBC-B 1609.1.2 |
| | PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS & |
| | CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, |
| | ADMINISTRATIVE CODE 61G20-3.005, SUB-CATEGORY OF |
| | PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE |
| | PRODUCT APPROVALS: |
| | (31)(B) WINDOWS. |
| | |
| | E-MAIL SENT 07/20/17 11:34 THERE MAYBE OTHER ISSUES |
| | THAT DEAL WITH THE REQUIRED FLOOR UNDELAYMENT SOUND |
| | REQUIREMENTS FOR THE 2ND FLOOR. |
| | |
| | 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | JAMES A. WITMER BN, PX, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |