| Plan Review Notes For Permit 17050878 |
| Permit Number |
17050878 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-06-02 11:05:49 | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70 2011 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | | | | ONLY ONE SET OF SPECS AND DRAWING HAVE BEEN SUBMITTED. | | | AT LEAST TWO SETS ARE REQUIRED. | | | | | | C405.2.4 EXTERIOR LIGHTING CONTROLS. | | | LIGHTING NOT DESIGNATED FOR DUSK-TO-DAWN OPERATION | | | SHALL BE CONTROLLED BY EITHER A COMBINATION OF A | | | PHOTOSENSOR AND A TIME SWITCH, OR AN ASTRONOMICAL TIME | | | SWITCH. LIGHTING DESIGNATED FOR DUSK-TO-DAWN | | | OPERATION SHALL BE CONTROLLED BY AN ASTRONOMICAL TIME | | | SWITCH OR PHOTOSENSOR. ALL TIME SWITCHES SHALL BE | | | CAPABLE OF RETAINING PROGRAMMING AND THE TIME SETTING | | | DURING LOSS OF POWER FOR A PERIOD OF AT LEAST 10 | | | HOURS. | | | | | | FBC 107.3.5.1.1(8) - PROVIDE WIND DESIGN LOADS/DESIGN | | | PRESSURES PURSUANT TO FBC-CHAPTER 16 |
|