| 2017-05-26 13:34:45 | 2014 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 17050856 |
| | ADD: 1645 PALM BEACH LAKES SUITE: 500 |
| | CONT: CHANDLER CONSTRUCTION |
| | TEL: 561-791-6934 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: FRI. MAY 26/ 2016 |
| | ACTION: DENIED |
| | HIGHRISE BUILDING |
| | 1) SHEET A-2 DETAIL # 2 THE PROPOSED FLOOR PLAN DOES |
| | NOT SHOW COMPLIANCE WITH 2014 FBC-B 713.14.1. EVERY |
| | ELEVATOR LOBBY SHALL HAVE AT ONE MEANS OF EGRESS, |
| | ENSURING THAT NO OCCUPANT FROM THE FLOOR HAS TO TRAVEL |
| | THROUGH THE ELEVATOR LOBBY TO AN EXIT. THERE APPEARS TO |
| | BE (2) POSSIBLE SOLUTIONS. THE FIRST WOULD BE TO CREATE |
| | A SECOND EXIT THROUGH ROOM # 114 INTO THE CORRIDOR YOU |
| | WOULD NOT HAVE TO TRAVEL THROUGH THE ELEVATOR LOBBY. |
| | THE 2ND SOLUTION WOULD BE TO INSTALL THE 1 HOUR RATED |
| | MAGNETIC DROPS FIRE AND SMOKE CURTAINS OVER EACH OF THE |
| | ELEVATOR OPENINGS. THE ELEVATOR FIRE AND SMOKE MAGNETIC |
| | CURTAIN WOULD HAVE TO BE TIED TO THE FIRE ALARM AS WELL |
| | TO ACTIVATE THE SYSTEM. |
| | |
| | 2) SHEET A-2 COMMON PATH OF TRAVEL HAS ALSO BEEN |
| | EXCEEDED. FROM THE OFFICE 112 MEASURING ONE FOOT FROM |
| | THE WALL FROM THE FURTHEST POINT IN THAT OFFICE TO |
| | WHERE YOU HAVE A CHOICE OF 2 EXITS THE TRAVEL DISTANCE |
| | IS APPROXIMATELY 113 FEET. TABLE 1014.3 OF THE 2014 |
| | FBC-B ONLY ALLOWS 100 FEET FOR FIRE SPRINKLERED |
| | BUILDINGS. PLEASE ALSO CHECK THE COMMON PATH OF TRAVEL |
| | FROM THE OTHER 3 CORNER OFFICES. |
| | |
| | 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | |
| | JAMES A. WITMER BN, PX, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |
| | DEPARTMENT |
| | 401 CLEMATIS ST. |
| | WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |