Plan Review Notes
Plan Review Notes For Permit 17050817
Permit Number 17050817
Review Stop B
Sequence Number 2
Notes
Date Text
2017-05-24 18:10:31RESIDENTIAL (R3) RE-ROOF SECOND BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 1- ORIGINAL COMMENT:
 NEED SIGNED AND SEALED RAS 117 CALCULATIONS (2 COPIES)
 AS REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF
 NOA 13-1022.15 SUBMITTED. NOTE: HOUSE IS LOCATED IN
 EXPOSURE "D". TAKE THIS INTO CONSIDERATION WHEN DOING
 THE CALCULATIONS. CALCULATIONS ARE REQUIRED TO MEET THE
 DESIGN PRESSURES OF SEC. R301.1 FBC RESIDENTIAL.
  
 RESPONSE:
 ENGINEER TO REVISE THE RAS 117 CALCULATIONS SUBMITTED:
 (A) ACCORDING TO SEC. R301.2.1.4 FBC-RESIDENTIAL, THIS
 BUILDING IS LOCATED IN EXPOSURE "D" NOT EXPOSURE "C".
 REVISE THE EXPOSURE AND THE DESIGN PRESSURES
 ACCORDINGLY.
 NOTE: THIS WAS NOTED ON MY ORIGINAL COMMENT TO HELP
 EXPEDITE THE REVIEW PROCESS.
  
 (B) SCOPE OF WORK IS NOT CLEAR. THIS IS NOT A "RECOVER"
 ROOF PROJECT. THIS IS A RE-ROOF PROJECT. SEE PRODUCT
 APPROVAL SUBMITTED AND REVISE AS REQUIRED. SEC. 107.2.1
 CITY AMENDMENTS.
  
 (C) SPECIFIC ROOFING ASSEMBLY TO BE INSTALLED IS NOT
 CLEAR. THE SYSTEM TYPE SPECIFIED BY THE ENGINEER IS: "A
 PAGE 6,7". THIS IS AN INSULATED SYSTEM. IT DOESN'T
 MATCH THE SYSTEM TYPE HIGHLIGHTED BY THE ROOFING
 CONTRACTOR. ROOFING CONTRACTOR HIGHLIGHTED A
 NON-INSULATED SYSTEM TYPE E ON PAGE 14 AND 15 OF 16.
 COORDINATE WITH ROOFING CONTRACTOR EXACT SYSTEM TO BE
 INSTALLED AND REVISE AS REQUIRED. SEC. 107.2.1 CITY
 AMENDMENTS.
  