Plan Review Notes
Plan Review Notes For Permit 17050813
Permit Number 17050813
Review Stop G
Sequence Number 3
Notes
Date Text
2017-09-22 15:44:571ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. GAS PLAN SHOWS TWO LOCATIONS OF TANKLESS WATER
 HEATER PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 2. PLEASE INDICATE LENGTH OF VENT AND INTAKE OF
 TANKLESS HEATER. FBC FG 502-505
  
 3. PROVIDE GAS RISER THAT CLEARLY SHOWS WERE THE BRANCH
 PIPE CONNECT AND WHAT ARE HORIZONTAL RUNS OR VERTICAL.
 FBC-2014 FUEL GAS, SECS. 402.4.1, 402.4.2.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
  