| Notes |
| Date |
Text |
| 2017-08-17 14:03:00 | 2ND REVIEW FBC-2014 MECHANICAL | | | REVISION #17050813 | | | MASTER #16090271 | | | 8/17/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE 1ST REVIEW COMMENT STILL EXISTS. I AM REPRINTING | | | IT BELOW- PLEASE COMPLY. | | | | | | 1) REFER TO SECTION G2407 FBC-14 RESIDENTIAL AND | | | INDICATE HOW COMBUSTION AIR IS BEING PROVIDED TO THE | | | RELOCATED GAS WATER IN THE GARAGE CLOSET. PLEASE | | | INCLUDE CALCULATIONS AND MANUFACTURER'S SPECIFICATIONS | | | FOR THE APPLIANCE. | | | | | | 2) SUBMITTAL OF PREVIOUSLY APPROVED STAMPED CITY PLANS | | | ARE NOT ACCEPTABLE FOR REVISION. PLEASE SUBMIT | | | UP-TO-DATE REVISED PLANS SIGNED BY THE DESIGNER OF | | | RECORD- SECTION 107.1 WPB AMENDMENTS TO THE FBC. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|