Plan Review Notes
Plan Review Notes For Permit 17050812
Permit Number 17050812
Review Stop B
Sequence Number 1
Notes
Date Text
2017-05-26 19:03:41PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT TWO SETS OF AN INSTALLATION SCHEDULE THAT
 CORRESPONDS WITH THE OPENING KEY PLAN FOR THE HURRICANE
 SHUTTERS. ON THE SCHEDULE, FOR EACH OPENING SPECIFY THE
 DESIGN PRESSURES, THE SPANS, THE EDGE DISTANCE, THE
 SUBSTRATE, THE CONNECTION TYPE (FROM THE PRODUCT
 APPROVAL), THE TYPE OF ANCHOR, THE ANCHOR SPACING, ETC.
 FBC 107.2.1 I HAVE INCLUDED A LINK TO THE CONSTRUCTION
 SERVICES DEPARTMENT SITE THAT HAS MANY OF THE RELATED
 FORMS INCLUDING THE SCHEDULE FOR INSTALLATION OF
 OPENING PROTECTIVE DEVICES.
 HTTP://WPB.ORG/DEVELOPMENT/FORMS-AND-PUBLICATIONS/
  
 2) INDICATE THE EMERGY EGRESS OPENING THAT WILL BE USED
 WHEN THE SHUTTERS ARE LOCKED IN PLACE. SHOW THAT THE
 EGRESS DOOR REQUIRED BY FBC - R311.1 WILL REMAIN IN
 COMPLIANCE WITH FBC- R311.2 AND BE READILY OPENABLE
 FROM INSIDE THE DWELLING WITHOUT THE USE OF A SPECIAL
 KEY OR SPECIAL KNOWLEDGE OR EFFORT WHEN THE STORM
 PANELS ARE IN PLACE.
  
  