| Plan Review Notes For Permit 17050794 |
| Permit Number |
17050794 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-05-24 07:16:10 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE NEW SINGLE HUNG WINDOW FOR OPENING NUMBER 3 DOES | | | NOT MEET THE REQUIREMENTS OF FBC R310 FOR EMERGENCY AND | | | RESCUE OPENINGS. INDICATE IF THERE IS ANOTHER OPENING | | | IN THIS BEDROOM THAT MEETS THE REQUIREMENTS OF R310. IF | | | THERE IS NO OTHER CODE COMPLIANT OPENING TO THE | | | EXTERIOR IN THE BEDROOM, THEN INDICATE THE EXISTING | | | WINDOW'S TYPE AND THE NET CLEAR OPENING SIZE OF IT. | | | PROVIDE CALCULATIONS TO SHOW THAT THE NET CLEAR OPENING | | | DIMENSIONS OF THE EXISTING WINDOW ARE NOT BEING REDUCED | | | BY MORE THAN 5-PERCENT PER FBC EXISTING BUILDING | | | SECTION 704.1. | | | | | | 2) INDICATE HOW AND WHERE THE MULLIONS WILL BE | | | INSTALLED. FBC 107.2.1 | | | | | | 3) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS | | | FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC | | | 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE | | | BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER | | | OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH | | | FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS | | | AND MAXIMUM DESIGN PRESSURES FOR THE IMPACT SLIDING | | | GLASS DOOR. |
|