Plan Review Notes
Plan Review Notes For Permit 17050772
Permit Number 17050772
Review Stop M
Sequence Number 1
Notes
Date Text
2017-06-06 16:40:161ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17050772
 6/6/17
  
 RESULTS: DENIED.
  
 1) THE SUBMITTED MECHANICAL PLANS FROM THE MAIN SET DO
 NOT SPECIFICALLY PROVIDE INFORMATION FOR THE PROPOSED
 KITCHEN EXHAUST HOOD AND SYSTEM. SUBMIT PLANS THAT SHOW
 THE LOCATIONS OF THE OVEN, THE EXHAUST HOOD, THE
 EXHAUST DUCT RUN FROM OUTLET TO TERMINATION, AND THE
 EXHAUST FAN,
  
 2) PROVIDE EQUIPMENT SCHEDULES FOR THE HOOD AND FAN.
 PLEASE NOTE THE FAN SCHEDULE ON M001 IS DESIGNATED "
 FOR REFERENCE ONLY".
  
 3) INDICATE HOW MAKEUP IS BEING PROVIDED FOR THE
 EXHAUST SYSTEM AND PROVIDE VENTILATION AND AIR BALANCE
 CALCULATIONS,
  
 4) PROVIDE CLEARANCE DISTANCE MEASUREMENTS FROM THE
 EXHAUST OUTLET TO MECHANICAL AND GRAVITY AIR INTAKES,
  
 5) THERE ARE PRODUCT DATA SUBMITTALS FOR AN INLINE
 EXHAUST FAN AND A SIDEWALL EXHAUST FAN- WHICH IS TO BE
 USED? THE EQUIPMENT SCHEDULE ON M001 INDICATES THE
 INLINE FAN. IF THAT IS THE CASE, PLEASE CLARIFY THE
 PURPOSE OF THE SIDEWALL FAN.
  
 6) A FL. LICENSED MECHANICAL CONTRACTOR MUST SUBMIT A
 PERMIT APPLICATION TO INSTALL THE EXHAUST HOOD AND
 DUCTWORK- SECTION 489.113(3) FLORIDA STAUTES.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  