| 2018-05-05 15:16:16 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | |
| | RESIDENTIAL (R3) ADDITION, BUILDING REVIEW COMMENTS |
| | CODE: FBC 5TH EDITION (2014). |
| | |
| | COMMENTS FROM PREVIOUS LIST: |
| | |
| | 1- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH |
| | COUNTY (2300 N. JOG RD.) FOR IMPACT FEES ASSESSMENT. |
| | BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID |
| | RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF |
| | THE UNIFIED LAND DEVELOPMENT CODE. |
| | |
| | 2ND REVIEW - THE PLANS WERE STAMPED BUT NO RECEIPT |
| | SHOWING THAT THE AMOUNT DUE OF $180.65 WAS PAID. PLEASE |
| | SEND VIA EMAIL. |
| | |
| | 2- PROVIDE ENERGY CALCULATIONS (2 COPIES) AS REQUIRED |
| | BY SEC. R101.4.3 FBC-ENERGY CONSERVATION, 5TH EDITION |
| | (2014). NOTE: PLEASE MAKE SURE CALCULATIONS ARE |
| | COMPLETE AND CORRECT. OWNER TO CERTIFY AT THE BOTTOM OF |
| | THE FORM CODE COMPLIANCE. |
| | |
| | 2ND REVIEW - ONLY ONE SET PROVIDED, NOT CERTIFIED |
| | (SIGNED) AT THE BOTTOM AS REQUIRED. |
| | |
| | 3- PROPOSED ADDITION IS LOCATED NEXT TO THE EXISTING |
| | MASTER BEDROOM. A WINDOW WAS ELIMINATED TO ALLOW FOR |
| | THE ADDITION. SHOW COMPLIANCE WITH THE BEDROOM EGRESS |
| | REQUIREMENTS. SPECIFY SIZE AND TYPE OF EXISTING BEDROOM |
| | WINDOW THAT IS GOING TO BE BLOCKED TO ALLOW FOR THE |
| | ADDITION. AND, SPECIFY SIZE AND TYPE OF ANY WINDOW ON |
| | THE REMAINING EXTERIOR BEDROOM WALL TO VERIFY |
| | COMPLIANCE WITH THE EGRESS REQUIREMENTS. SEC. 704 |
| | FBC-EXISTING BUILDING, 5TH EDITION (2014) AND SEC. R310 |
| | FBC-RESIDENTIAL, 5TH EDITION (2014). |
| | |
| | 2ND REVIEW - A 37" X 51" "EGRESS TYPE" WINDOW |
| | SPECIFIED. PROVIDE SPEC SHEETS FROM MANUFACTURER TO |
| | SHOW COMPLIANCE. WINDOW HEIGHT APPEARS NON COMPLIANT. |
| | |
| | 4-5 OK |
| | |
| | 6- ENGINEER OF RECORD TO CLEARLY SPECIFY TYPE OF |
| | WINDOWS TO BE INSTALLED. ARE THEY FIXED OR OPERABLE |
| | WINDOWS?. SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | SINGLE HUNG SPECIFIED, AWNING NON IMPACT PRODUCT |
| | APPROVALS SUBMITTED. IF ALL COMMENTS ARE ADDRESSED NEXT |
| | REVIEW, THIS WILL BE ISSUED WITH PROVISO THAT PRODUCT |
| | APPROVALS FOR PROPOSED WINDOWS ARE SUBMITTED AFTER |
| | ISSUANCE PRIOR TO INSTALLATION, IMPACT PROTECTION |
| | REQUIRED. |
| | |
| | 7-8 OK |
| | |
| | 9 OK |
| | |
| | 10 PRODUCT APPROVALS; SEE ITEM 6 - IF COMPLIANT PRODUCT |
| | APPROVALS ARE NOT PROVIDED PRIOR TO ISSUANCE, THEY WILL |
| | BE REQUIRED TO BE SUBMITTED, REVIEWED, AND APPROVED |
| | PRIOR TO INSTALLATION. FEES MAY APPLY. |
| | SINGLE HUNG PRODUCT APPROVAL REQUIRED, NON IMPACT |
| | AWNING SUBMITTED |
| | NON IMPACT PRODUCTS REQUIRE IMPACT PROTECTION |
| | DOOR SUBMITTED IS WRONG CODE (EXPIRED) |
| | ROOF OK |
| | |
| | 11- OK |
| | |
| | NEW COMMENT |
| | |
| | 12. THIS IS AN OWNER BUILDER PERMIT APPLICATION, BUT NO |
| | OWNER BUILDING AFFIDAVIT WAS FOUND IN THE FILE. OWNER |
| | BUILDING IS REQUIRED TO APPEAR AT THE BUILDING DIVISION |
| | TO SIGN PER FS553. |
| | |
| | ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | |