Plan Review Notes
Plan Review Notes For Permit 17050761
Permit Number 17050761
Review Stop P
Sequence Number 1
Notes
Date Text
2017-06-12 15:30:161ST REVIEW: FBC 2014 5TH EDITION
  
 1. WASHING MACHINE DRAIN ID IS NOT VENTED . PER FBC RES
 P3101.2.1
  
 2. THE FIXTURE BRANCH FOR WASHING MACHINE SHALL CONNECT
 TO BUILDING DRAIN DOWN STREAM OF BATHROOM GROUP. PER
 FBC RES P3108.1
  
 3. THE TUB AND SHOWER DRAIN SHALL CONNECT SEPARATELY TO
 WET VENT.PER FBC RES P3108.1
  
 4. SHOWER SHALL HAVE SEPARATE TRAP. PER FBC RES P3201.6
  
 5. SHOW DIRECTION OF BUILDING DRAIN ON RISER DIAGRAM.
 PER WPB AND TO FBC 107.2.1
  
 PLUMBING COMMENTS:
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  