2017-06-08 18:35:42RESIDENTIAL (R3) ADDITION, MECHANICAL REVIEW COMMENTS
 CODE: FBC 5TH EDITION (2014).
  
 1- HVAC PLAN SHOWN ON SHEET 2 IS INCOMPLETE. SPECIFY
 WHERE IS THE DUCTWORK COMING FROM. IS IT FROM EXISTING
 A/C UNIT?. IS IT A NEW A/C INSTALLATION?. SPECIFY CFM'S
 FOR EACH ROOM. SPECIFY ON PLANS THE EXISTING OR THE
 PROPOSED EQUIPMENT MANUFACTURER AND MODEL NUMBER. NOTE:
 COORDINATE WITH ITEM # 3 BELOW. SEC. 107.3.5.3(10) CITY
 AMENDMENTS.
  
 2- REVISE HVAC PLAN. RETURN AIR CAN NOT BE TAKING FROM
 BATHROOM AND ALL OTHER ROOMS SPECIFIED ON SEC. M1602.2
 OF FBC-RESIDENTIAL, 5TH EDITION (2014). REVISE AS
 REQUIRED.
  
 3- PROVIDE COMPLETE EQUIPMENT LOAD CALCULATIONS TO SHOW
 THAT EXISTING UNIT IS CAPABLE OF SUPPORTING THE
 ADDITIONAL LOAD. OR, IF NEW UNIT IS REQUIRED. SPECIFY
 EQUIPMENT MANUFACTURER AND MODEL NUMBER. SEC. R403.6.1
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 4- MECHANICAL PERMIT IS REQUIRED. SEC. 105.1 CITY
 AMENDMENTS.
  
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
  