Plan Review Notes
Plan Review Notes For Permit 17050748
Permit Number 17050748
Review Stop M
Sequence Number 2
Notes
Date Text
2017-08-30 11:45:06PLAN DENIED
 1) PROVIDE A SIGNATURE ON THE MECHANICAL PLAN
 OF THE PERSON WHO DREW THE PLAN AND TAKING
 RESPONSIBILITY
 OF THE DESIGN. PLAN CAN NOT BE DROWN ON ENGINEER PAPER
 UNLESS ENGINEER DREW THE PLAN, IF THE ENGINEER DREW THE
 PLAN
 STAMP OR SEAL WOULD BE REQUIRED.
 SECTION 107.2.1 FBC 2014
 2) PROVIDE EQUIPMENT SCHEDULE ON PLAN. 107 FBC
 3) SHOW LOCATION OF CONDENSERS ON PLAN 107 FBC
 4) REFER TO SECTION M1503.4 MAKE UP AIR REQUIRED
 PROVIDE EXHAUST HOOD SPECIFICATIONS WITH THE PLAN.
 2014 RESIDENTIAL CODE.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-85-6676
  