| Plan Review Notes For Permit 17050734 |
| Permit Number |
17050734 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-05-22 16:22:49 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) THE SUBMITTED PLANS ARE TOO SMALL AND UNREADABLE. | | | | | | PLEASE ENLARGE. | | | | | | | | | | | | 2) THESE PLANS APPEAR FOR SEPARATE INSTALLTIONS. LOW | | | VOLTAGE ACCESS CONTROL AND GARAGE DOORS. | | | | | | PLEASE CLARIFY, IF CORRECT, THESE SHOULD SEPARATE | | | PERMITS. | | | | | | | | | | | | 3) NO MANUFACTURES SPECS WERE SUBMITTED FOR THE ACCESS | | | CONTROL. | | | | | | PLEASE PROVIDE. | | | | | | | | | | | | 4) ACCESS CONTROL SHALL COMPLY WITH NFPA 101, CHAPTER | | | 7, MEANS OF EGRESS. | | | | | | PROVIDE APPLICABLE NOTE OF COMPLIANCE. | | | | | | | | | | | | 5) IF NEW GATES ARE PROPOSED PLEASE PROVIDE GREATER | | | DETAIL WITH A SITE PLAN AND CONSTRUCTION DOCUMENTS. | | | | | | PLEASE PROVIDE DETAILS. | | | | | | | | | | | | 6) IS THERE FIRE SPRINKLERS IN THIS OCCUPANCY. IF SO, | | | THE GATES MAY BE AN OBSTRUCTION AND FIRE SPRINKLER WORK | | | IS REQUIRED THROUGH SEPARATE SHOP DRAWINGS. | | | | | | PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE OF | | | COMPLIANCE | | | | | | | | | 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|