Plan Review Notes
Plan Review Notes For Permit 17050734
Permit Number 17050734
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2017-05-22 16:22:49THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THE SUBMITTED PLANS ARE TOO SMALL AND UNREADABLE.
  
 PLEASE ENLARGE.
  
  
  
 2) THESE PLANS APPEAR FOR SEPARATE INSTALLTIONS. LOW
 VOLTAGE ACCESS CONTROL AND GARAGE DOORS.
  
 PLEASE CLARIFY, IF CORRECT, THESE SHOULD SEPARATE
 PERMITS.
  
  
  
 3) NO MANUFACTURES SPECS WERE SUBMITTED FOR THE ACCESS
 CONTROL.
  
 PLEASE PROVIDE.
  
  
  
 4) ACCESS CONTROL SHALL COMPLY WITH NFPA 101, CHAPTER
 7, MEANS OF EGRESS.
  
 PROVIDE APPLICABLE NOTE OF COMPLIANCE.
  
  
  
 5) IF NEW GATES ARE PROPOSED PLEASE PROVIDE GREATER
 DETAIL WITH A SITE PLAN AND CONSTRUCTION DOCUMENTS.
  
 PLEASE PROVIDE DETAILS.
  
  
  
 6) IS THERE FIRE SPRINKLERS IN THIS OCCUPANCY. IF SO,
 THE GATES MAY BE AN OBSTRUCTION AND FIRE SPRINKLER WORK
 IS REQUIRED THROUGH SEPARATE SHOP DRAWINGS.
  
 PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE OF
 COMPLIANCE
  
  
 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  