| 2017-06-02 15:02:04 | CODES IN EFFECT: |
| | FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| | EDITION |
| | NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | |
| | ELECTRICAL 1ST REVIEW COMMENTS: |
| | |
| | 1. PROVIDE 2 COPIES OF PLAN FOR REVIEW. FBC 107.1 |
| | 2. SHOW AFCI PROTECTION PER CODE. ALL 120-VOLT, SINGLE |
| | PHASE, 15 AND 20 AMPERE BRANCH CIRCUITS SUPPLYING |
| | OUTLETS IN DWELLING UNIT FAMILY ROOMS, DINING ROOMS, |
| | LIVING ROOMS, PARLORS, LIBRARIES, DENS, BEDROOMS, |
| | SUNROOMS, RECREATION ROOMS, CLOSETS, HALLWAYS, OR |
| | SIMILAR AREAS OR ROOMS, SHALL HAVE AFCI PROTECTION. NEC |
| | 210.12, FBC RE3902.12 |
| | 3. PROVIDE PANEL SCHEDULE, INDICATE WIRE AND BREAKER |
| | SIZE FOR EACH CIRCUIT TO BE INSTALLED. NEC 215.5, 408.4 |
| | 4. PROVIDE SMOKE ALARM FOR BASEMENT LEVEL. FBC |
| | R314.3(3). |
| | 5. PROVIDE CO ALARM WITHIN 10 FEET OF SLEEPING ROOMS. |
| | FBC R315.1 |
| | 6. PROVIDE LIGHT AT EXTERIOR DOOR TO BASEMENT. FOR |
| | DWELLING UNITS, ATTACHED GARAGES, AND DETACHED GARAGES |
| | WITH ELECTRIC POWER, AT LEAST ONE WALL |
| | SWITCH-CONTROLLED LIGHTING OUTLET SHALL BE INSTALLED ON |
| | THE EXTERIOR SIDE OF OUTDOOR ENTRANCES OR EXITS WITH |
| | GRADE LEVEL ACCESS. NEC 210.70(A)(2)(B), FBC RE3903.3 |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |