Plan Review Notes
Plan Review Notes For Permit 17050706
Permit Number 17050706
Review Stop E
Sequence Number 1
Notes
Date Text
2017-05-26 07:35:24FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PROVIDE CUT SHEETS FOR FIXTURES, TIME CLOCK AND/OR
 PHOTOCELL.
  
 FBC-EC405.2.4 EXTERIOR LIGHTING CONTROLS.
 LIGHTING NOT DESIGNATED FOR DUSK-TO-DAWN OPERATION
 SHALL BE CONTROLLED BY EITHER A COMBINATION
 OF A PHOTOSENSOR AND A TIME SWITCH, OR AN ASTRONOMICAL
 TIME SWITCH. LIGHTING DESIGNATED FOR
 DUSK-TO-DAWN OPERATION SHALL BE CONTROLLED BY AN
 ASTRONOMICAL TIME SWITCH OR PHOTOSENSOR.
 ALL TIME SWITCHES SHALL BE CAPABLE OF RETAINING
 PROGRAMMING AND THE TIME SETTING DURING LOSS
 OF POWER FOR A PERIOD OF AT LEAST 10 HOURS.
  
  