| 2017-06-21 11:53:01 | 2ND REVIEW FBC-2014 MECHANICAL | | | PERMIT #17050701 | | | 6/21/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) MANY NEW SPEC SHEETS FOR EQUIPMENT WERE SUBMITTED | | | INCLUDING THE VULCAN OVEN, THE REVENT OVEN, THE STONE | | | HEARTH OVEN, TWO DIFFERENT PROOFING CABINERS, THE APEX | | | REFRIGERATION SYSTEM ETC. PLEASE SHOW AND LABEL ALL THE | | | EQUIPMENT LOCATIONS ON SHEET A211, AND PROVIDE AN | | | EQUIPMENT SCHEDULE ON THE PLAN. | | | | | | 2) SHEET M1.1: SECOND REQUEST TO SHOW HOW COMBUSTION | | | AIR FOR THE NEW ROTARY OVEN IS BEING PROVIDED. THE | | | DESIGN PROFESSIONALS NARRATIVE IS POINTING TO THE OVEN | | | EXHAUST EXHAUST VENT IN RESPONSE TO THE COMMENT. | | | | | | 3) M1.1: AS PREVIOUSLY REQUESTED INDICATE HOW MAKE-UP | | | AIR FOR THE REVENT OVEN IS BEING PROVIDED. THE BUILDING | | | PRESSURIZATION TABLE ON M0.1 INDICATES MUA AT 883 CFMS | | | WITHOUT SHOWING HOW THAT AIR IS BEING SUPPLIED. | | | | | | 4) DUCT SMOKE DETECTORS ARE REQUIRED IN THE RETURN AIR | | | SYSTEMS OF AHU-1 & 2 PER SECTION 606.2.1. PLEASE NOTE | | | THAT A TYPICAL 5-TON AIR HANDLER CAN PRODUCE SUPPLY AIR | | | IN EXCESS OF 2000 CFMS DESPITE THE DESIGN CAPACITIES | | | SHOWN IN THE AC SCHEDULE. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|