Plan Review Notes
Plan Review Notes For Permit 17050701
Permit Number 17050701
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2017-06-19 12:07:332ND REVIEW
  
 THE COMMENTS PROVIDED BY FIRE WERE NOT SPECIFICALLY
 ADDRESSED AND SHALL BE PROVIDED WITH THE REQUIRED
 PROVISIONS AND/OR CLARIFIED WITH CODE REFERENCES.
  
  
  
 1) SHEET A 210 - THERE ARE INCORRECT REFERENCES TO THE
 FLORIDA FIRE PREVENTION CODE EDITION; 2010.
  
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING
 THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER
 APPLICABLE CODES OR STANDARDS.
  
 FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 13, 2010 EDITION.
 FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 72, 2010 EDITION.
 CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 241, 2009 EDITION.
  
 PLEASE PROVIDE AN APPLICABLE NOTE OF COMPLIANCE.
  
  
  
 2) SHEET A 210 - THE DOOR SCHEDULE DOES NOT SHOW ANY
 HARDWARE AND/OR EXIT HARDWARE.
  
 PLEASE RECIEW AND CORRECT.
  
  
  
  
 3) SHEET A 210 - THE OCCUPANCY CLASSIFICATION IS NOTED
 AS BUSINESS; HOWEVER, A STORAGE, EMPLOYEE LOUNGE, A
 BUSINESS OFFICE, AND A BAKERY WITH SEATING OVER 50 IS
 INDICATED.
  
 PLEASE PROVIDE WHAT THE OCCUPANCY CLASSIFICATION IS AND
 WHETHER IT IS MIXED OR SEPARATED PER NFPA 101.
  
 6.1.14 MULTIPLE OCCUPANCIES.
 6.1.14.1 GENERAL.
 6.1.14.1.1 MULTIPLE OCCUPANCIES SHALL COMPLY WITH THE
 REQUIREMENTS OF 6.1.14.1 AND ONE OF THE FOLLOWING:
 (1) MIXED OCCUPANCIES ? 6.1.14.3
 (2) SEPARATED OCCUPANCIES ? 6.1.14.4
 6.1.14.1.2 WHERE EXIT ACCESS FROM AN OCCUPANCY
 TRAVERSES ANOTHER OCCUPANCY, THE MULTIPLE OCCUPANCY
 SHALL BE TREATED AS A MIXED OCCUPANCY.
 6.1.14.1.3* WHERE INCIDENTAL TO ANOTHER OCCUPANCY,
 AREAS USED AS FOLLOWS SHALL BE PERMITTED TO BE
 CONSIDERED PART OF THE PREDOMINANT OCCUPANCY AND SHALL
 BE SUBJECT TO THE PROVISIONS OF THE CODE THAT APPLY TO
 THE PREDOMINANT OCCUPANCY:
 (1) MERCANTILE, BUSINESS, INDUSTRIAL, OR STORAGE USE
 (2)* NONRESIDENTIAL USE WITH AN OCCUPANT LOAD FEWER
 THAN THAT ESTABLISHED BY SECTION 6.1 FOR THE OCCUPANCY
 THRESHOLD
 (3) PORTIONS OF BUILDINGS USED AS ACCESSORY OFFICES OR
 FOR CUSTOMARY NON-HAZARDOUS USES NECESSARY FOR
 TRANSACTING THE PRINCIPAL BUSINESS IN STORAGE AND
 INDUSTRIAL OCCUPANCIES NEED NOT BE SEPARATED FROM THE
 PRINCIPAL USE.
 (4) INDUSTRIAL OCCUPANCIES PRODUCING, USING, OR STORING
 LOW HAZARD PRODUCTS IN ACCORDANCE WITH SUBDIVISION
 6.2.2 NEED NOT BE SEPARATED BY FIRE-RESISTANT
 CONSTRUCTION FROM THE OCCUPANCIES TO WHICH THEY ARE
 ACCESSORY.
 6.1.14.1.3.1 INCIDENTAL USE AREAS SHALL BE SEPARATED AS
 REQUIRED BY TABLE 508.2.5 OF THE FLORIDA BUILDING CODE
 WHERE TABLE 508.2.5 PERMITS AN AUTOMATIC
 FIRE-EXTINGUISHING SYSTEM WITHOUT A FIRE BARRIER, THE
 INCIDENTAL USE AREA SHALL BE SEPARATED BY CONSTRUCTION
 CAPABLE OF RESISTING THE PASSAGE OF SMOKE.
  
  
  
  
 4) THERE IS NO LIFE SAFETY PLAN SHEET PROVIDED.
  
 BASED ON WHAT OCCUPANCY CLASSIFICATION NOTED FOR # 3
 ABOVE, COMPLETE LIFE SAFETY PLANS FOR EACH OCCUPANCY
 SHALL BE PROVIDED THAT ILLUSTRATE OCCUPANT LOADS,
 TRAVEL DISTANCES, COMMON PATHS OF TRAVEL, DEAD-END
 CORRIDORS, EXIT SIGNS, EMERGENCY LIGHTING, EXITS
 LEADING TO A PUBLIC WAY, FIRE EXTINGUISHER LOCATIONS,
 AND ALL FIRE SAFETY FEATURES AND EQUIPMENT.
  
 NFPA 1
  
 1.7.11 PLANS AND SPECIFICATIONS.
 1.7.11.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH
 APPLICABLE CODES AND STANDARDS.
  
 1.7.11.5 PLANS SHALL BE SUBMITTED TO THE AHJ PRIOR TO
 THE CHANGE OF OCCUPANCY OF ANY EXISTING BUILDING.
 1.7.11.6 PLANS SHALL BE SUBMITTED TO THE AHJ PRIOR TO
 THE ALTERATION OF THE MEANS OF EGRESS OR FIRE
 PROTECTION SYSTEMS OF ANY EXISTING BUILDING.
 1.7.11.7 PLANS SHALL BE SUBMITTED TO THE AHJ FOR OTHER
 CONDITIONS AS DEEMED NECESSARY BY THE AHJ TO DETERMINE
 COMPLIANCE WITH THE APPLICABLE CODES AND STANDARDS.
  
 PLEASE ENSURE ALL INDICATED EXITS LEAD TO A PUBLIC WAY.
  
 3.3.81* EXIT. THAT PORTION OF A MEANS OF EGRESS THAT IS
 SEPARATED FROM ALL OTHER SPACES OF A BUILDING OR
 STRUCTURE BY CONSTRUCTION OR EQUIPMENT AS REQUIRED TO
 PROVIDE A PROTECTED WAY OF TRAVEL TO THE EXIT
 DISCHARGE.
 3.3.82 EXIT ACCESS. THAT PORTION OF A MEANS OF EGRESS
 THAT LEADS TO AN EXIT.
 3.3.83 EXIT DISCHARGE. THAT PORTION OF A MEANS OF
 EGRESS BETWEEN THE TERMINATION OF AN EXIT AND A PUBLIC
 WAY.
  
 PLEASE PROVIDE A LIFE SAFETY PLAN.
  
  
  
  
 5) SHEET A 210 - A MEZZANINE IS INDICATED WITH ONLY ONE
 EXIT THAT PASSES THROUGH ANOTHER OCCUPANCY
 CLASSIFICATION.
  
 PER NFPA 1 -
  
 14.9.1 GENERAL.
 14.9.1.1 THE NUMBER OF MEANS OF EGRESS FROM ANY
 BALCONY, MEZZANINE, STORY, OR PORTION THEREOF SHALL BE
 NOT LESS THAN TWO, EXCEPT UNDER ONE OF THE FOLLOWING
 CONDITIONS:
 (1) A SINGLE MEANS OF EGRESS SHALL BE PERMITTED WHERE
 PERMITTED IN CHAPTERS 11 THROUGH 43 OF NFPA 101.
 (2) A SINGLE MEANS OF EGRESS SHALL BE PERMITTED FOR A
 MEZZANINE OR BALCONY AND THE COMMON PATH OF TRAVEL
 LIMITATIONS OF CHAPTERS 11 THROUGH 43 OF NFPA 101 ARE
 MET. [101:7.4.1.1]
  
 NFPA 101
  
 8.6.10 MEZZANINES.
 8.6.10.1 GENERAL. MULTILEVEL RESIDENTIAL HOUSING AREAS
 IN DETENTION AND CORRECTIONAL OCCUPANCIES IN ACCORDANCE
 WITH CHAPTERS 22 AND 23 SHALL BE EXEMPT FROM THE
 PROVISIONS OF
 8.6.10.2 AND 8.6.10.3.
 8.6.10.2 AREA LIMITATIONS.
 8.6.10.2.1 THE AGGREGATE AREA OF MEZZANINES LOCATED
 WITHIN A ROOM, OTHER THAN THOSE LOCATED IN
 SPECIAL-PURPOSE INDUSTRIAL OCCUPANCIES, SHALL NOT
 EXCEED ONE-THIRD THE OPEN AREA OF THE ROOM IN WHICH THE
 MEZZANINES ARE LOCATED. ENCLOSED SPACE SHALL NOT BE
 INCLUDED IN A DETERMINATION OF THE SIZE OF THE ROOM IN
 WHICH THE MEZZANINE IS LOCATED.
  
 8.6.10.3 OPENNESS. THE OPENNESS OF MEZZANINES SHALL BE
 IN ACCORDANCE WITH 8.6.10.3.1 OR 8.6.10.3.2.
 8.6.10.3.1 ALL PORTIONS OF A MEZZANINE, OTHER THAN
 WALLS NOT MORE THAN 42 IN. (1065 MM) HIGH, COLUMNS, AND
 POSTS, SHALL BE OPEN TO AND UNOBSTRUCTED FROM THE ROOM
 IN WHICH THE MEZZANINE IS LOCATED, UNLESS THE OCCUPANT
 LOAD OF THE AGGREGATE AREA OF THE ENCLOSED SPACE DOES
 NOT EXCEED 10.
  
 PLEASE ENSURE THIS MEZZANINE AND PROPOSED OCCUPANCY
 CLASSIFICATION MEETS THE REQUIREMENT OF THE PROPOSED
 OCCUPANCY PER # 3 ABOVE.
  
  
  
  
  
 6) SHEET 210 - A KITCHEN AREA IS INDICATED WITH SEVERAL
 OVENS NOTED
  
 NFPA 101
  
 9.2.3 COMMERCIAL COOKING EQUIPMENT. COMMERCIAL COOKING
 EQUIPMENT SHALL BE IN ACCORDANCE WITH NFPA 96, STANDARD
 FOR VENTILATION CONTROL AND FIRE PROTECTION OF
 COMMERCIAL COOKING OPERATIONS, UNLESS SUCH
 INSTALLATIONS ARE APPROVED EXISTING INSTALLATIONS,
 WHICH SHALL BE PERMITTED TO BE CONTINUED IN SERVICE.
  
 NFPA 96
  
 CHAPTER 4 GENERAL REQUIREMENTS
 4.1 GENERAL.
 4.1.1 COOKING EQUIPMENT USED IN PROCESSES PRODUCING
 SMOKE OR GREASE-LADEN VAPORS SHALL BE EQUIPPED WITH AN
 EXHAUST SYSTEM THAT COMPLIES WITH ALL THE EQUIPMENT AND
 PERFORMANCE REQUIREMENTSOF THIS STANDARD.
  
 ALL KITCHEN EQUIPMENT AND OPERATIONS SHALL COMPLY WITH
 NFPA 96, STANDARD FOR VENTILATION CONTROL AND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS.
 EXTINGUISHMENT AND VENTILATION SYSTEM SHOP DRAWINGS
 SHALL BE SUBMITTED SEPARATELY FOR APPROVAL.
  
 PLEASE PROVIDE AN APPLICABLE NOTE OF COMP[LIANCE.
  
  
  
  
  
 7) SHEET A 210 - A STAIR FROM THE MEXXANINE IS
 INDICATED. IT APPEARS TO BE OPEN.
  
 PER NFPA 101
  
 7.2.2.5 ENCLOSURE AND PROTECTION OF STAIRS.
 7.2.2.5.1 ENCLOSURES.
 7.2.2.5.1.1 ALL INSIDE STAIRS SERVING AS AN EXIT OR
 EXIT COMPONENT SHALL BE ENCLOSED IN ACCORDANCE WITH
 7.1.3.2.
  
 PLEASE PROVIDE FOR THE REQUIREMENTS AND/OR CLARIFY.
  
  
  
  
 8) SHEET A 210 - A STAIR FROM THE MEXXANINE IS
 INDICATED. THERE IS NO STAIR DETAIL, INCLUDING
 RAILINGS, GAURDS AND/OR HAND RAILS THAT MEET THE
 REQUIREMENTS OF NFPA 101, CHAPTER 7 MEANS OF EGRESS.
  
 PLEASE PROVIDE.
  
  
  
 9) SHEET A 211 - THERE IS A NOTE INDICATING "UNDER
 STAIR CART PARKING". THERE SHALL BE NOT COMBUSTIBLES
 STORED UNDER STAIRS.
  
 PER NFPA 101 -
  
 7.2.2 STAIRS.
 7.2.2.1 GENERAL.
 7.2.2.1.1 STAIRS USED AS A COMPONENT IN THE MEANS OF
 EGRESS SHALL CONFORM TO THE GENERAL REQUIREMENTS OF
 SECTION 7.1 AND TO THE SPECIAL REQUIREMENTS OF 7.2.2,
 UNLESS OTHERWISE SPECIFIED IN 7.2.2.1.2.
  
  
 7.2.2.5.3* USABLE SPACE. ENCLOSED, USABLE SPACES WITHIN
 EXIT ENCLOSURES SHALL BE PROHIBITED, INCLUDING UNDER
 STAIRS, UNLESS OTHERWISE PERMITTED BY 7.2.2.5.3.2.
 7.2.2.5.3.1 OPEN SPACE WITHIN THE EXIT ENCLOSURE SHALL
 NOT BE USED FOR ANY PURPOSE THAT HAS THE POTENTIAL TO
 INTERFERE WITH EGRESS.
 7.2.2.5.3.2 ENCLOSED, USABLE SPACE SHALL BE PERMITTED
 UNDER STAIRS, PROVIDED THAT BOTH ALL OF THE FOLLOWING
 CRITERIA ARE MET:
 (1) THE SPACE SHALL BE SEPARATED FROM THE STAIR
 ENCLOSURE BY THESAME FIRE RESISTANCE AS THE EXIT
 ENCLOSURE.
 (2) ENTRANCE TO THE ENCLOSED, USABLE SPACE SHALL NOT BE
 FROM WITHIN THE STAIR ENCLOSURE. (SEE ALSO 7.1.3.2.3.)
 (3) THE SPACE IS NOT USED FOR THE STORAGE OF FLAMMABLE,
 OR OTHERWISE HAZARDOUS MATERIALS.
  
 PLEASE PROVIDE FOR THE REQUIREMENTS AND/OR CLARIFY
  
  
  
  
 10) SHEET E 2.1 - EXIT SIGNS ARE INDICATED OVER SEVERAL
 DOORS.
  
 PLEASE ENSURE ALL INDICATED EXITS LEAD TO A PUBLIC WAY
 AS PER # 4 ABOVE.
  
 3.3.81* EXIT. THAT PORTION OF A MEANS OF EGRESS THAT IS
 SEPARATED FROM ALL OTHER SPACES OF A BUILDING OR
 STRUCTURE BY CONSTRUCTION OR EQUIPMENT AS REQUIRED TO
 PROVIDE A PROTECTED WAY OF TRAVEL TO THE EXIT
 DISCHARGE.
 3.3.82 EXIT ACCESS. THAT PORTION OF A MEANS OF EGRESS
 THAT LEADS TO AN EXIT.
 3.3.83 EXIT DISCHARGE. THAT PORTION OF A MEANS OF
 EGRESS BETWEEN THE TERMINATION OF AN EXIT AND A PUBLIC
 WAY.
  
  
  
 11) A FIRE SPRINKLER SYSTEM IS INDICATED.
  
 ALL WORK ON THE FIRE SPRINKLER SYSTEM SHALL BE DONE
 UNDER SEPARATE SHOP DRAWINGS BY CERTIFIED LIFE SAFETY
 CONTRACTORS
  
 PLEASE PROVIDE AN APPLICABLE NOTE
  
  
  
  
 12) THERE IS NO INDICATIONS OF A FIRE ALARM SYSTEM.
  
 ALL WORK ON THE FIRE ALARM SYSTEM SHALL BE DONE UNDER
 SEPARATE SHOP DRAWINGS BY CERTIFIED LIFE SAFETY
 CONTRACTORS
  
 PLEASE PROVIDE AN APPLICABLE NOTE.
  
  
  
 13) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 14) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  