Plan Review Notes
Plan Review Notes For Permit 17050701
Permit Number 17050701
Review Stop P
Sequence Number 1
Notes
Date Text
2017-05-23 13:22:281ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS: DENIED 5/23/17
  
 1.SHT. P0.2 THE BRANCH DRAIN FOR THE URINAL SHALL
 CONNECT DOWN STREAM OF THE LAVATORY'S IT CAN NOT
 CONNECT TO WET VENT PER FBC PL 912.1
  
 2. TEMPERED WATER IS REQUIRED ON PUBLIC LAVATORY'S PER
 FBC PL
  
 3 BACKFLOW REQUIRED ON WATER SUPPLY TO OVEN PROFFER AND
 ESPRESSO MACHINE. PER FBC PL 608.3
  
 4. SHUT OFF VALVES ARE REQUIRED ON THE HOT AND COLD
 DROPS TO ISLAND WITH ESPRESSO AND DRINK MACHINES. PER
 FBC PL 606.1
  
 5. ONE OF THE VENTS FOR GREASE SYSTEM SHALL TERMINATE
 OUTDOORS. PER FBC PL 904.1
  
 6. PLACE A NOTE ON THE PLAN THAT AN INSPECTION ON THE
 EXISTING GREASE INTERCEPTOR SHALL BE COMPLETED BY
 UTILITIES PRIOR TO FINAL PLUMBING INSPECTION, THE OWNER
 CAN CONNECT JEFF ODOMS AT 822-2172 OR [email protected] TO
 SCHEDULE AN INSPECTION WITH UTILITIES.
  
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  