2017-05-23 07:47:061ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17050701
 5/23/17
  
 RESULTS: DENIED.
  
 1) THERE APPEARS TO BE CONFLICTING AND INCOMPLETE
 INFORMATION ON THE PLAN REGARDING HOW OUTSIDE AIR IS
 BEING PROVIDED TO THE VARIOUS ROOMS AND SPACES SHOWN ON
 THE LAYPOUT PLAN. REGARDING AHU-1 THE CALCULATIONS ON
 M0.1 INDICATE NATURAL VENTILATION FOR THE SEATING AREA
 , HOWEVER THERE IS AN O/A DUCT CONNECTED TO AHU-1 WHICH
 IS THE MECHANICAL UNIT SUPPLYING CONDITIONED AIR
  
 TO BOTH THE SERVING AND SEATING AREA. THE CALCULATIONS
 ARE ALSO INDICATING 250 CFMS OF O/A SUPPLIED BY AHU-1
 TO THE CORRIDOR, HOWEVER THERE IS NO CORRIDOR SHOWN ON
 THE PLAN IN THE AREA OF AHU-1. REGARDING AHU-2 THE
 CALCULATIONS ARE INDICATING 250 CFMS OF O/A TO THE
 CORRIDOR AND STORAGE ARE. THIS APPEARS INCOMPLETE
 BECAUSE THE AREAS BEING SERVED BY AHU-2 ALSO INCLUDE
 THE
  
 SERVICE AND KITCHEN AREAS, AND MEZZANINE AREA.
  
 2) EXHAUST VENTILATION AT A RATE OF .70 CFMS PER SQ.
 FT. IS REQUIRED FOR THE KITCHEN AREA PER TABLE 403.3.
 PLEASE PROVIDE THE MEANS AND A CALCULATION.
  
 3) PROVIDE EQUIPMENT SCHEDULES FOR THE TWO GAS-FIRED
 OVENS ON THE PLAN AND SUBMIT PRODUCT DATA SHEETS FOR
 EACH.
  
 4) INDICATE HOW COMBUSTION AIR IS BEING PROVIDED TO THE
 TWO GAS-FIRED OVENS AND PROVIDE CALCULATIONS- SECTION
 304 FBC-14 FUEL GAS.
  
 5) PROVIDE VENTING PLANS FOR THE TWO OVENS THAT
 INDICATE THE TYPES AND SIZES OF VENT, VENT RUNS, AND
 TERMINATION LOCATIONS- SEE SECTIONS 502, 503, & 504
 FBC-14 FUEL GAS.
  
 6) PROVIDE AIR BALANCE CALCULATIONS.
  
 7) PLEASE NOTE THAT SEPARATE PERMITS ARE REQUIRED FOR
 KITCHEN EXHAUST HOODS, FIRE SUPRESSION SYSTEMS, AND
 WALK-IN COOLERS AND FREEZERS. PLEASE PLACE NOTES ON THE
 PLAN ACCORDINGLY.
  
 8) SHOW THE ACTUAL LOCATIONS ON THE ROOF WHERE THE TWO
 AC CONDENSERS WILL BE INSTALLED INCLUDING CLEARANCE
 DISTANCE MEASUREMENTS FROM ROOF EDGES.
  
 9) SUBMIT THE NOA'S FOR THE AC STANDS, AND O/A LOUVERS
 WITH APPROVAL SIGNATURES AND MARK-UPS BY THE EOR.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  