| 2017-05-23 07:47:06 | 1ST REVIEW FBC-2014 MECHANICAL |
| | PERMIT #17050701 |
| | 5/23/17 |
| | |
| | RESULTS: DENIED. |
| | |
| | 1) THERE APPEARS TO BE CONFLICTING AND INCOMPLETE |
| | INFORMATION ON THE PLAN REGARDING HOW OUTSIDE AIR IS |
| | BEING PROVIDED TO THE VARIOUS ROOMS AND SPACES SHOWN ON |
| | THE LAYPOUT PLAN. REGARDING AHU-1 THE CALCULATIONS ON |
| | M0.1 INDICATE NATURAL VENTILATION FOR THE SEATING AREA |
| | , HOWEVER THERE IS AN O/A DUCT CONNECTED TO AHU-1 WHICH |
| | IS THE MECHANICAL UNIT SUPPLYING CONDITIONED AIR |
| | |
| | TO BOTH THE SERVING AND SEATING AREA. THE CALCULATIONS |
| | ARE ALSO INDICATING 250 CFMS OF O/A SUPPLIED BY AHU-1 |
| | TO THE CORRIDOR, HOWEVER THERE IS NO CORRIDOR SHOWN ON |
| | THE PLAN IN THE AREA OF AHU-1. REGARDING AHU-2 THE |
| | CALCULATIONS ARE INDICATING 250 CFMS OF O/A TO THE |
| | CORRIDOR AND STORAGE ARE. THIS APPEARS INCOMPLETE |
| | BECAUSE THE AREAS BEING SERVED BY AHU-2 ALSO INCLUDE |
| | THE |
| | |
| | SERVICE AND KITCHEN AREAS, AND MEZZANINE AREA. |
| | |
| | 2) EXHAUST VENTILATION AT A RATE OF .70 CFMS PER SQ. |
| | FT. IS REQUIRED FOR THE KITCHEN AREA PER TABLE 403.3. |
| | PLEASE PROVIDE THE MEANS AND A CALCULATION. |
| | |
| | 3) PROVIDE EQUIPMENT SCHEDULES FOR THE TWO GAS-FIRED |
| | OVENS ON THE PLAN AND SUBMIT PRODUCT DATA SHEETS FOR |
| | EACH. |
| | |
| | 4) INDICATE HOW COMBUSTION AIR IS BEING PROVIDED TO THE |
| | TWO GAS-FIRED OVENS AND PROVIDE CALCULATIONS- SECTION |
| | 304 FBC-14 FUEL GAS. |
| | |
| | 5) PROVIDE VENTING PLANS FOR THE TWO OVENS THAT |
| | INDICATE THE TYPES AND SIZES OF VENT, VENT RUNS, AND |
| | TERMINATION LOCATIONS- SEE SECTIONS 502, 503, & 504 |
| | FBC-14 FUEL GAS. |
| | |
| | 6) PROVIDE AIR BALANCE CALCULATIONS. |
| | |
| | 7) PLEASE NOTE THAT SEPARATE PERMITS ARE REQUIRED FOR |
| | KITCHEN EXHAUST HOODS, FIRE SUPRESSION SYSTEMS, AND |
| | WALK-IN COOLERS AND FREEZERS. PLEASE PLACE NOTES ON THE |
| | PLAN ACCORDINGLY. |
| | |
| | 8) SHOW THE ACTUAL LOCATIONS ON THE ROOF WHERE THE TWO |
| | AC CONDENSERS WILL BE INSTALLED INCLUDING CLEARANCE |
| | DISTANCE MEASUREMENTS FROM ROOF EDGES. |
| | |
| | 9) SUBMIT THE NOA'S FOR THE AC STANDS, AND O/A LOUVERS |
| | WITH APPROVAL SIGNATURES AND MARK-UPS BY THE EOR. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |